Approved Document M: access to and use of buildings, volume 1: dwellings

Library captured 10 September 2026 · Source updated 30 September 2024

The Building Regulations 2010

#

Source page 1

Access to and use of buildings

APPROVED DOCUMENT

Volume 1: Dwellings

M4(1)Category 1: Visitable dwellings

M4(2)Category 2: Accessible and adaptable dwellings

M4(3)Category 3: Wheelchair user dwellings

2015 edition incorporating 2016 amendments – for use in England*

Main changes in the 2015 edition

#

Source page 2

This volume of this approved document supports requirements M4(1), M4(2) and M4(3) of Schedule 1 to the Building Regulations 2010. It takes effect on 1 October 2015 for use in England*. The 2004 edition of Approved Document M with 2010 and 2013 amendments will continue to apply to work started before 1 October 2015 or work subject to a building notice, full plans application or initial notice submitted before that date.

The main changes are:

Approved Document M has been split into two parts:

Volume 1: Dwellings

Volume 2: Buildings other than dwellings.

Requirement M4 ‘Sanitary conveniences in dwellings’ has been replaced by new requirements:

M4(1) Category 1: Visitable dwellings

M4(2) Category 2: Accessible and adaptable dwellings

M4(3) Category 3: Wheelchair user dwellings.

Regulation M4(1) is mandatory for all new dwellings unless one of the optional requirements M4(2) or M4(3) applies.

Main changes made by the 2016 amendments

The changes are corrections and clarifications, as set out in the 2016 AD M Volume 1 Corrigenda.

* This approved document gives guidance for compliance with the Building Regulations for building work carried out in England. It also applies to building work carried out on excepted energy buildings in Wales as defined in the Welsh Ministers (Transfer of Functions) (No.2) Order 2009.

The approved documents

#

Source page 3

What is an approved document?

The Secretary of State has approved a series of documents that give practical guidance about how to meet the requirements of the Building Regulations 2010 for England. Approved documents give guidance on each of the technical parts of the regulations and on regulation 7 (see the back of this document).

Approved documents set out what, in ordinary circumstances, may be accepted as reasonable provision for compliance with the relevant requirements of the Building Regulations to which they refer. If you follow the guidance in an approved document, there will be a presumption of compliance with the requirements covered by the guidance. However, compliance is not guaranteed; for example, ‘normal’ guidance may not apply if the particular case is unusual in some way.

Note that there may be other ways to comply with the requirements – there is no obligation to adopt any particular solution contained in an approved document. If you prefer to meet a relevant requirement in some other way than described in an approved document, you should discuss this with the relevant building control body.

In addition to guidance, some approved documents include provisions that must be followed exactly, as required by regulations or where methods of test or calculation have been prescribed by the Secretary of State.

Each approved document relates only to the particular requirements of the Building Regulations that the document addresses. However, building work must also comply with any other applicable requirements of the Building Regulations.

How to use this approved document

This document uses the following conventions.

a.Text against a green background is an extract from the Building Regulations 2010 or the Building (Approved Inspectors etc.) Regulations 2010 (both as amended). These extracts set out the legal requirements of the regulations.

b.Key terms, printed in green, are defined in Appendix A.

c.When this approved document refers to a named standard or other document, the relevant version is listed in Appendix B (standards) or Appendix C (other documents). However, if the issuing body has revised or updated the listed version of the standard or document, you may use the new version as guidance if it continues to address the relevant requirements of the Building Regulations.

Where you can get further help

#

Source page 4

If you do not understand the technical guidance or other information in this approved document or the additional detailed technical references to which it directs you, you can seek further help through a number of routes, some of which are listed below.

a.The Government website: www.gov.uk

b.If you are the person undertaking the building work: either from your local authority building control service or from an approved inspector

c.If you are registered with a competent person scheme: from the scheme operator

d.If your query is highly technical: from a specialist or an industry technical body for the relevant subject.

The Building Regulations

#

Source page 5

The following is a high level summary of the Building Regulations relevant to most types of building work. Where there is any doubt you should consult the full text of the regulations, available at www.legislation.gov.uk.

Building work

Regulation 3 of the Building Regulations defines ‘building work’. Building work includes:

a.the erection or extension of a building

b.the provision or extension of a controlled service or fitting

c.the material alteration of a building or a controlled service or fitting.

Regulation 4 states that building work should be carried out in such a way that, when work is complete:

a.For new buildings or work on a building that complied with the applicable requirements of the Building Regulations: the building complies with the applicable requirements of the Building Regulations.

b.For work on an existing building that did not comply with the applicable requirements of the Building Regulations:

(i)the work itself must comply with the applicable requirements of the Building Regulations

(ii)the building must be no more unsatisfactory in relation to the requirements than before the work was carried out.

Material change of use

Regulation 5 defines a ‘material change of use’ in which a building or part of a building that was previously used for one purpose will be used for another.

The Building Regulations set out requirements that must be met before a building can be used for a new purpose. To meet the requirements, the building may need to be upgraded in some way.

Materials and workmanship

In accordance with regulation 7, building work must be carried out in a workmanlike manner using adequate and proper materials. Guidance on materials and workmanship is given in Approved Document 7.

Energy efficiency requirements

Part 6 of the Building Regulations imposes additional specific requirements for energy efficiency.

If a building is extended or renovated, the energy efficiency of the existing building or part of it may need to be upgraded.

Notification of work

#

Source page 6

Most building work and material changes of use must be notified to a building control body unless one of the following applies.

a.It is work that will be self-certified by a registered competent person or certified by a registered third party.

b.It is work exempted from the need to notify by regulation 12(6A) of, or Schedule 4 to, the Building Regulations.

Responsibility for compliance

People who are responsible for building work (e.g. agent, designer, builder or installer) must ensure that the work complies with all applicable requirements of the Building Regulations. The building owner may also be responsible for ensuring that work complies with the Building Regulations. If building work does not comply with the Building Regulations, the building owner may be served with an enforcement notice.

Contents

#

Source page 7

The approved documents Page i

The Building Regulations iii

Section 0: Approved Document M. Volume 1: Access to and use of dwellings 1

Summary 1

Application 1

Optional requirements 1

Interaction with other legislation 1

Mixed use development 2

Material alterations 2

Historic buildings 2

Interaction with Parts C and K of the Building Regulations 2

Requirement M4(1): Category 1 – Visitable dwellings 3

Performance 3

Section 1: Category 1 – Visitable dwellings 4

Section 1A: Approach to the dwelling 4

Application 4

Approach routes 4

Communal entrances 5

Communal lifts and stairs 6

Section 1B: Private entrances and spaces within the dwelling 7

Application 7

Private entrances 7

Circulation areas and internal doorways 7

Sanitary facilities 8

Services and controls 9

Optional requirement M4(2): Category 2 – Accessible and adaptable dwellings 10

Performance 10

Section 2: Category 2 – Accessible and adaptable dwellings 11

Page 8

#

Source page 8

11Section 2A: Approach to the dwelling

11Application

11Approach routes

13Car parking and drop-off

14Communal entrances

15Communal lifts and stairs

16Section 2B: Private entrances and spaces within the dwelling

16Application

16Private entrances

17Circulation areas and internal doorways

18Habitable rooms

19Sanitary facilities

22Services and controls

23Optional requirement M4(3): Category 3 – Wheelchair user dwellings

23Performance

24Section 3: Category 3 – Wheelchair user dwellings

24Section 3A: Approach to the dwelling

24Application

24Approach routes

27Car parking and drop-off

27Communal entrances

28Communal lifts and stairs

30Section 3B: Private entrances and spaces within, and connected to, the dwelling

30Application

30Private entrances

32Circulation areas, internal doorways and storage

36Habitable rooms

40Sanitary facilities

49Services and controls

50Private outdoor space

51Appendix A: Key terms

54Appendix B: Standards referred to

55Appendix C: Other documents referred to

56Appendix D: Furniture schedule

57Index

Section 0: Approved Document M Volume 1: Access to and use of dwellings

#

Source page 9

Summary

0.1This approved document gives guidance about how to comply with requirements M4(1), M4(2) and M4(3) of the Building Regulations. It contains the following sections:

Section 1: Category 1 – Visitable dwellings

Section 2: Category 2 – Accessible and adaptable dwellings

Section 3: Category 3 – Wheelchair user dwellings

Application

0.2The recommendations of this volume of this approved document apply to newly erected dwellings, and dwellings undergoing material alteration, only. They do not apply to the extension of a dwelling.

Optional requirements

0.3Requirements M4(2) and M4(3) are ‘optional requirements’ as defined in the Building Regulations. An optional requirement only applies where a condition that one or more dwellings should meet the relevant optional requirement is imposed on new development as part of the process of granting planning permission. Where no condition is imposed, dwellings only need to meet requirements M4(1). Compliance should be assessed against only one of requirements M4(1), M4(2) or M4(3) for any given dwelling.

0.4Where any part of an approach route, including vertical circulation in the common parts of a block of flats, is shared between dwellings of different categories, Section A of the optional requirement for the highest numbered category of dwelling served will apply to that part of the approach route.

0.5Where a local planning authority sets a planning condition for Category 3 (wheelchair user) housing it can specify which dwellings should be wheelchair accessible by including in the planning permission a condition stating that optional requirement M4(3)(2)(b) applies. Where no such condition is applied, optional requirement M4(3)(2)(a) will apply by default requiring that dwellings should be wheelchair adaptable.

0.6The person carrying out building work must inform the building control body where any optional requirements apply.

Interaction with other legislation

The Workplace (Health, Safety and Welfare) Regulations

0.7If people, such as cleaners and caretakers, are employed to work in the common parts of flats and similar buildings the Workplace (Health, Safety and Welfare) Regulations will apply.

0.8The Workplace (Health, Safety and Welfare) Regulations contain some requirements that affect building design. The main requirements are covered by the Building Regulations. For further information see www.hse.gov.uk.

The Equality Act 2010 and Equality Act 2010 (Disability) Regulations

#

Source page 10

0.9Those who dispose of, let or manage premises are subject to the provisions in Part 4 of the Equality Act 2010. The Act protects people who meet the Act’s definition of a disabled person from disability discrimination, harassment and victimisation. The provisions in Part 4 of the Act do not apply to the erection of new dwellings.

Mixed use development

0.10Common areas in mixed use development containing both domestic and non domestic functions should meet the requirements for non-domestic buildings in Approved Document M: Volume 2.

Material alterations

0.11Where a dwelling is subject to a material alteration, the building should be no less compliant with requirement M4(1) than it was prior to the building work taking place.

Historic buildings

0.12Historic buildings include listed buildings, buildings in conservation areas, buildings of architectural merit referred to as a material consideration in a Local Plan, buildings of architectural and historic merit within national parks, areas of outstanding natural beauty, world heritage sites and vernacular buildings of traditional form and construction.

0.13Requirements for accessibility should be balanced against preserving historic buildings or environments. In achieving an appropriate balance it would be appropriate to take into account the advice of the local authority’s conservation and access officers, English Heritage and the views of local access groups.

Interaction with Parts C and K of the Building Regulations

0.14Requirements M4(1), M4(2) and M4(3) of Part M set out requirements for stepped and ramped approaches forming part of accessible approach routes in and around dwellings. Part K sets out requirements for stepped or ramped approaches which form part of a building other than where the requirements of Part M are applicable. Where both Part M and Part K apply, requirement M4(1), M4(2) or M4(3) as appropriate of Part M takes precedence.

0.15In meeting the provisions of Part M by providing a level or ramped approach and level threshold, care must be taken to ensure the moisture resistance and design of the dwelling as a whole also complies with requirements C2 and C4.

Requirement M4(1): Category 1 – Visitable dwellings

#

Source page 11

This section of the approved document deals with the following requirement from Part M of Schedule 1 to the Building Regulations 2010.

Requirement
RequirementLimits on application
Category 1 – visitable dwelling Access and use M4(1). Reasonable provision should be made for people to— (a) gain access to; and (b) use, the dwelling and its facilitiesRequirement M4(1) does not apply to: (a) an extension to a dwelling; or (b) any part of a building that is used solely to enable the building or any service or fitting in the building to be inspected, repaired or maintained.

*Requirement*

*Limits on application*

Performance

In the Secretary of State’s view, requirement M4(1) will be met when a new dwelling makes reasonable provision for most people, including wheelchair users, to approach and enter the dwelling and to access habitable rooms and sanitary facilities on the entrance storey. Reasonable provision is made if the dwelling complies with all of the following.

a.Within the curtilage of the dwelling or the building containing the dwelling, it is possible to approach and gain access to the dwelling.

b.It is possible to gain access to the dwelling, or the building containing the dwelling, from the most likely point of alighting from a car.

c.A disabled person who is able to walk is able to visit any dwelling in a building containing one or more dwellings.

d.Visitors can access and use the habitable rooms and a WC within the entrance storey of the dwelling (or the principal storey where the entrance storey does not contain a habitable room).

e.Where the habitable rooms and the WC are located on the entrance storey, access between them is step free.

f.Wall-mounted switches and socket outlets in habitable rooms are reasonably accessible to people who have reduced reach.

Section 1: Category 1 – Visitable dwellings

#

Source page 12

Section 1A: Approach to the dwelling

Application

1.1The provisions of Section 1A apply to external and internal areas and elements that form part of the approach route to the dwelling and fall within the plot (or curtilage) of the individual dwelling, or the building containing the dwelling.

1.2Where parking is not provided within the curtilage, the provisions apply to the approach route between the dwelling and the nearest point at which a visitor, including a disabled person, would expect to get in and out of a car. This point of access may be within or outside the plot of the dwelling, or the building containing the dwelling (such as a block of flats). These provisions do not apply beyond the curtilage of the development.

Approach routes

General

1.3The approach route should be safe and convenient for everyone, including older and disabled people and some wheelchair users. It should adopt the shallowest gradient that can reasonably be achieved and be step-free where possible.

1.4The approach route should be level, gently sloping, or, where necessary, ramped. On steeply sloping plots, a stepped approach can be used.

1.5Normally these provisions will apply to the principal private entrance but where this is not possible, access to a suitable alternative entrance would be reasonable.

1.6To enable most people to approach the dwelling, approach routes should comply with all of the following.

a.The approach route is level, gently sloping, ramped or, where unavoidable, stepped.

b.All external parts of the approach route have a suitable ground surface.

c.The approach route is a minimum of 900mm wide with a maximum cross fall of 1 in 40.

d.Where a driveway forms all, or part of, the approach route, an additional allowance of at least 900mm wide should be provided so that a wheelchair user can pass a parked car.

External ramps forming part of an approach route

1.7A ramped approach should comply with all of the following.

a.Individual flights are:

for gradients up to 1:15 – not more than 10m long

for gradients up to 1:12 – not more than 5m long

b.Every flight has a minimum clear width of 900mm.

External stepped approach

#

Source page 13

c.Every flight has a top and bottom landing.

d.An intermediate landing is provided between individual flights and at any change of direction.

e.Every landing is a minimum of 1200mm long, clear of the swing of any door (or gate).

External stepped approach

1.8Where it is not possible to achieve step-free access to any private entrance (as may occur on a steeply sloping plot) a stepped approach is acceptable if it complies with all of the following.

a.Steps are uniform with a rise of 75-150mm and a minimum going of 280mm (for tapered steps measured at a point 270mm from the ‘inside’ (narrow end) of the step).

b.Steps have suitable tread nosings.

c.No individual flight has a rise of more than 1800mm between landings.

d.Every flight has a minimum clear width of 900mm.

e.Top and bottom and, where necessary, intermediate landings, are provided and every landing has a minimum length of 900mm.

f.Every flight with three or more risers has a suitable handrail to one side. This grippable handrail is 850-1000mm above the pitch line of the flight and extends a minimum of 300mm beyond the top and bottom nosings.

Communal entrances

1.9The principal communal entrance door of the building containing the dwelling should comply with all of the following.

a.The door has a minimum clear opening width of 775mm, when measured in accordance with Diagram 1.1.

Door plan diagram showing the measurement of clear opening width between the inside face of an open door and the inside edge of the door frame or stop, with key and notes.
Diagram 1.1 Measurement of clear opening width of external and internal doors

b.Any threshold is an accessible threshold.

c.The ground surface (or entrance flooring) does not impede wheelchairs.

Communal lifts and stairs

#

Source page 14

General provisions

1.10A passenger lift is the most convenient way for many people to move from one storey to another. Where a lift is provided, it should be suitable for a wheelchair user. Where lift access cannot reasonably be achieved it is acceptable to provide a suitable stair.

Communal passenger lifts

1.11A suitable lift should comply with all of the following.

a.There is a clear landing a minimum 1500mm long and 1500mm wide directly in front of the lift door at every floor level.

b.The load capacity is at least 400kg.

c.The doors have a minimum clear opening width of 800mm.

d.The car is a minimum 900mm wide and 1250mm deep inside.

e.Tactile indication, to identify each storey, is provided on the landing and adjacent to the lift call button.

f.Tactile indication, to confirm the floor selected, is provided on, or adjacent to, the lift buttons within the car.

g.The lift incorporates a signalling system that gives visual notification that the lift is answering a landing call.

h.The lift has a dwell time of five seconds before its doors begin to close after they are fully open.

i.The system can be overridden by a door re-activating device that relies on appropriate electronic methods (but not a door edge pressure system); provided that the lift door remains fully open for at least three seconds.

j.When the lift serves more than three storeys, it provides visual and audible indicators to identify the floor reached.

k.Landing and car controls are between 900mm and 1200mm above the car floor and a minimum 400mm (measured horizontally) from the inside of the front wall.

Communal stairs

1.12The principal communal stairs that give access to the dwelling should comply with one of the following:

a.Where the dwelling is on an upper floor and does not have lift access, the stair meets the requirements of Part K for a general access stair.

b.Where the dwelling is on an upper floor and does have lift access, the stair meets the requirements of Part K for a utility stair.

Section 1B: Private entrances and spaces within the dwelling

#

Source page 15

Application

1.13Except where noted, the provisions of Section 1B apply to the principal private entrance and to key areas within the entrance storey (or where there are no habitable rooms on the entrance storey, the principal storey) of the dwelling. This applies to all dwelling types, including upper floor flats.

Private entrances

1.14The principal private entrance to the dwelling (or the alternative entrance where the approach route is not to the principal private entrance) should comply with all of the following.

a.The door has a minimum clear opening width of 775mm, when measured in accordance with Diagram 1.1.

b.Any threshold is an accessible threshold.

c.Where a step into the dwelling is unavoidable, the rise is a maximum 150mm and is aligned with the outside face of the door threshold.

Circulation areas and internal doorways

Door and hall widths

1.15To facilitate access into habitable rooms and to a WC in the entrance storey, door and hall widths should comply with all of the following (see Diagram 1.2).

a.Every door to a habitable room and the room containing the WC has a minimum clear opening width as set out in Table 1.1, when measured in accordance with Diagram 1.1.

b.Any localised obstruction, such as a radiator, does not occur opposite or close to a doorway, and is no longer than 2m in length; and the corridor is not reduced below a minimum 750mm width at any point.

Plan diagram showing minimum door widths, corridor widths, and permitted and prohibited zones for localised obstructions.
Diagram 1.2 Minimum door width, hall widths and localised obstructions

Private stairs and changes of level within the entrance storey

#

Source page 16

Table 1.1 Minimum widths of corridors and passageways for a range of doorway widths
Doorway clear opening width (mm)Corridor clear passageway width (mm)
750 or wider900 (when approached head on)
7501200 (when approach is not head-on)
7751050 (when approach is not head-on)
800900 (when approach is not head on)

Private stairs and changes of level within the entrance storey

1.16To provide easy access between rooms on the entrance storey, a stepped change of level within the entrance storey should be avoided where possible. If internal steps or stairs on the entrance level are unavoidable, they should comply with the provisions of Part K.

Sanitary facilities

WC facilities

1.17To enable easy access to a WC, a dwelling should comply with all of the following.

a.A room (which may be a WC/cloakroom or a bathroom) containing a WC is provided on the entrance storey or, where there are no habitable rooms on the entrance storey, on the principal storey or the entrance storey.

b.There is clear space to access the WC in accordance with Diagram 1.3.

c.Any basin is positioned to avoid impeding access.

d.The door to the room opens outwards and has a clear opening width in accordance with Table 1.1.

Two WC plan examples showing clear access zones for oblique transfer and frontal transfer, with minimum dimensions and notes.
Diagram 1.3 WC access zones

Services and controls

#

Source page 17

Two WC or cloakroom plan examples showing oblique access and frontal access, with dimensions and notes that dimensions are for illustration purposes only and doors should open outwards.
Diagram 1.4 Examples of WC/cloakrooms

Services and controls

1.18To assist people who have reduced reach, services and controls should comply with all of the following.

a.Switches and sockets, including door bells, entry phones, light switches, power sockets, TV aerials and telephone jacks, serving habitable rooms throughout the dwelling have their centre line 450-1200mm above floor level, as shown in Diagram 1.5.

b.Consumer units are mounted so that the switches are 1350-1450mm above floor level.

Elevation diagram showing the height range from 450mm to 1200mm above floor level for switches, sockets, door bells, entry phones, TV sockets and telephone jack points.
Diagram 1.5 Heights of switches, sockets etc.

Optional requirement M4(2): Category 2 – Accessible and adaptable dwellings

#

Source page 18

This section of the approved document deals with the following optional requirement from Part M of Schedule 1 to the Building Regulations 2010.

RequirementLimits on application
Optional requirement Part M access to and use of buildings Category 2 – accessible and adaptable dwellings M4(2) optional requirement (1) Reasonable provision must be made for people to— (a) gain access to; and (b) use, the dwelling and its facilities. (2) The provision made must be sufficient to— (a) meet the needs of occupants with differing needs, including some older or disabled people; and (b) to allow adaptation of the dwelling to meet the changing needs of occupants over time.Optional requirement M4(2)— (a) may apply only in relation to a dwelling that is erected; (b) will apply in substitution for requirement M4(1); (c) does not apply where optional requirement M4(3) applies; (d) does not apply to any part of a building that is used solely to enable the building or any service or fitting in the building to be inspected, repaired or maintained.

Performance

In the Secretary of State’s view, optional requirement M4(2) will be met where a new dwelling makes reasonable provision for most people to access the dwelling and incorporates features that make it potentially suitable for a wide range of occupants, including older people, those with reduced mobility and some wheelchair users. Reasonable provision is made if the dwelling complies with all of the following.

a.Within the curtilage of the dwelling, or of the building containing the dwelling, it is possible to approach and gain step-free access to the dwelling and to any associated parking space and communal facilities intended for the occupants to use.

b.There is step-free access to the WC and other accommodation within the entrance storey, and to any associated private outdoor space directly connected to the entrance storey.

c.A wide range of people, including older and disabled people and some wheelchair users, are able to use the accommodation and its sanitary facilities.

d.Features are provided to enable common adaptations to be carried out in future to increase the accessibility and functionality of the dwelling.

e.Wall-mounted switches, socket outlets and other controls are reasonably accessible to people who have reduced reach.

Section 2: Category 2 – Accessible and adaptable dwellings

#

Source page 19

Section 2A: Approach to the dwelling

Application

2.1The provisions of Section 2A apply only where a planning condition requires compliance with optional requirement M4(2) for accessible and adaptable dwellings (see paragraphs 0.3 to 0.6).

2.2The provisions of Section 2A apply to external and internal areas and elements that form part of the approach route to the individual dwelling and fall within the plot (or curtilage) of the dwelling or the building containing the dwelling.

2.3The provisions also apply to the approach route between the dwelling and the point, or points, at which an occupant or visitor, including a disabled person, would expect to get in and out of a car. This point, or points, of access may be within or outside the plot of the dwelling or the building containing the dwelling (typically a block of flats). These provisions do not apply beyond the curtilage of the development.

2.4Reasonable provision should be made to ensure that the approach route to any communal facilities that serve the dwelling meets these provisions. Communal facilities include storage areas, such as those used for depositing refuse and recycling, but not plant rooms or other service areas unless occupants need regular access, for example for meter reading.

2.5For a house (or other dwelling that sits within its own plot) the approach route will often only involve a driveway, or a gate and a path, but for a dwelling within a larger building (typically a block of flats) the approach route will usually involve one, or more, communal gates, paths, entrances, doors, lobbies, corridors and access decks, as well as communal lifts and stairs.

Approach routes

General

2.6The approach route should be safe and convenient, adopt the shallowest gradient that can reasonably be achieved and be step-free, irrespective of the storey on which the dwelling is located.

2.7Where it is not reasonable to achieve a step-free approach route to the principal private entrance, a step-free approach route should be provided to a suitable alternative private entrance instead. The provisions for approach routes (other than those relating specifically to step-free access) should still apply to both the route to the principal private entrance and the route to the alternative private entrance.

2.8Where a communal ramped approach route is provided and has an overall rise of 300mm or more, an additional stepped route meeting the requirements of paragraph 2.11 should also be provided.

External and internal ramps forming part of an approach route

#

Source page 20

2.9An approach route for a Category 2 dwelling should comply with all of the following.

a.The approach route is level, gently sloping or, where necessary, ramped.

b.Private parts of the approach route have a minimum clear width of 900mm or 750mm where there are localised obstructions.

c.Communal parts of the approach route (except communal stairs) have a minimum clear width of 1200mm or 1050mm where there are localised obstructions.

d.Any localised obstruction does not occur opposite or close to a doorway, or at a change of direction, and is no longer than 2m in length.

e.All external parts of the approach route have a suitable ground surface.

f.Every gate (or gateway) along the approach route has both:

a minimum clear opening width of 850mm

a 300mm nib to the leading edge of the gate.

External and internal ramps forming part of an approach route

2.10To enable people to use a ramp safely, the ramp should comply with all of the following.

a.The gradient is between 1:20 and 1:12.

b.The length of each flight at a given gradient meets the provisions of Diagram 2.1.

c.Flights within a private approach route have a minimum clear width of 900mm.

d.Flights within a communal approach route have a minimum clear width of 1200mm.

Ramp gradient chart showing maximum ramp flight lengths, rises, notes, and satisfactory and non-compliant zones.
Diagram 2.1 Maximum length of ramp at a given gradient

External steps forming part of an additional route

#

Source page 21

e.Every flight has a top and bottom landing.

f.An intermediate landing is provided between individual flights and at any change of direction.

g.Every landing is a minimum 1200mm long, clear of any door (or gate) swing.

External steps forming part of an additional route

2.11To enable a wide range of people to use steps safely, a stepped approach should comply with all of the following.

a.Steps are uniform with a rise of between 150mm and 170mm and a going of between 280mm and 425mm (for tapered steps measured at a point 270mm from the ‘inside’ (narrow end) of the step).

b.Steps have suitable tread nosings.

c.No individual flight has a rise between landings of more than 1800mm.

d.Every flight has a minimum clear width of 900mm.

e.Top and bottom and, where necessary, intermediate landings are provided and every landing has a minimum length of 900mm.

f.Every flight with three or more risers has a suitable grippable handrail to one side, (or to both sides where the flight is wider than 1000mm). This grippable handrail is 850-1000mm above the pitch line of the flight and extends a minimum of 300mm beyond the top and bottom nosings.

Car parking and drop-off

Parking space

2.12Where a parking space is provided for the dwelling, it should comply with all of the following.

a.Where the parking is within the private curtilage of the dwelling (but not within a carport or garage) at least one space is a standard parking bay that can be widened to 3.3m.

b.Where communal parking is provided to blocks of flats, at least one standard parking bay is provided close to the communal entrance of each core of the block (or to the lift core where the parking bay is internal). The parking bay should have a minimum clear access zone of 900mm to one side and a dropped kerb in accordance with paragraph 2.13d.

c.Access between the parking bay and the principal private entrance or, where necessary, the alternative private entrance to the dwelling is step free.

d.The parking space is level or, where unavoidable, gently sloping.

e.The gradient is as shallow as the site permits.

f.The parking space has a suitable ground surface.

Drop-off point

2.13Where a drop-off point is provided for the dwelling, it should comply with all of the following.

a.It is located close to the principal communal entrance of the building containing the dwelling.

b.It is level or, where unavoidable, gently sloping.

c.It has a suitable ground surface.

Communal entrances

#

Source page 22

d.Where a dropped kerb is provided, it is a minimum of 1000mm wide, reasonably flush with the adjoining ground and has a maximum gradient of 1:12.

Communal entrances

Principal communal entrance

2.14The principal communal entrance should comply with all of the following.

a.There is a level landing a minimum of 1500mm wide and 1500mm long directly outside the entrance and clear of the swing of any door.

b.The landing is covered to a minimum width of 1200mm and depth of 900mm.

c.Lighting is provided which uses fully diffused luminaires activated automatically by a dusk to dawn timer or by detecting motion.

d.The entrance door (or gate) has a minimum clear opening width of 850mm, when measured in accordance with Diagram 2.2.

e.Where there are double doors (or gates), the main (or leading) leaf provides the required minimum clear opening width.

f.A minimum 300mm nib is provided to the leading edge of the door (or gate) and the extra width created by this nib is maintained for a minimum distance of 1200mm beyond it.

g.The reveal on the leading side of the door (usually the inside) has a maximum depth of 200mm.

h.The threshold is an accessible threshold.

i.Where there is a lobby or porch, the doors are a minimum of 1500mm apart and there is a minimum of 1500mm between door swings.

j.The ground surface (or entrance flooring) does not impede wheelchair movement.

k.Door entry controls, where provided, are mounted 900-1000mm above finished ground level, and at least 300mm away from any projecting corner.

Doorway plan diagram showing clear opening width, door edges, nib, reveal depth, key, and measurement notes.
Diagram 2.2 Measurement of clear opening width and other features of external and internal doors

Other communal doors

#

Source page 23

2.15Every communal door, or gate, along the approach route should comply with provisions d. to k. of paragraph 2.14.

Communal lifts and stairs

Communal lifts

2.16A wide range of people, including accompanied wheelchair users, should be able to access and use the lift. Every passenger lift that gives access to the dwelling should comply with all of the following.

a.There is a clear landing, a minimum of 1500mm long and 1500mm wide, directly in front of the lift door at every floor level.

b.The lift is equivalent to or meets the requirements of BS EN 81-70:2003 for a type 2 lift.

c.The car is a minimum of 1100mm wide and 1400mm deep inside.

d.Doors have a minimum clear opening width of 800mm.

e.Landing and car controls are 900-1200mm above the car floor and a minimum of 400mm (measured horizontally) from the inside of the front wall.

f.The lift has an initial dwell time of five seconds before its doors begin to close after they are fully open.

Communal stairs

2.17The principal communal stair that gives access to the dwelling should meet the requirements of Part K for a general access stair.

Section 2B: Private entrances and spaces within the dwelling

#

Source page 24

Application

2.18The provisions of Section 2B apply only where a planning condition requires compliance with optional requirement M4(2) for accessible and adaptable dwellings (see paragraphs 0.3 to 0.6).

2.19The provisions of Section 2B apply to private entrances, other external doors and key elements within the dwelling.

Private entrances

Principal private entrance and alternative entrance

2.20The principal private entrance, or the alternative private entrance where step-free access cannot be achieved to the principal private entrance, should comply with all of the following.

a.There is a level external landing with a minimum width and depth of 1200mm.

b.The landing is covered for a minimum width of 900mm and a minimum depth of 600mm.

c.Lighting is provided which uses fully diffused luminaires activated automatically by a dusk to dawn timer or by detecting motion.

d.The door has a minimum clear opening width of 850mm when measured in accordance with Diagram 2.2.

e.Where there are double doors, the main (or leading) leaf provides the required minimum clear opening width.

f.A minimum 300mm nib is provided to the leading edge of the door and the extra width created by this nib is maintained for a minimum distance of 1200mm beyond it.

g.The depth of the reveal on the leading side of the door (usually the inside) is a maximum of 200mm

h.The threshold is an accessible threshold.

i.Where there is a lobby or porch, the doors are a minimum of 1500mm apart and there is at least 1500mm between door swings.

Other external doors

2.21All other external doors – including doors to and from a private garden, balcony, terrace, garage, carport, conservatory or storage area that is integral with, or connected to, the dwelling – should comply with provisions d. to i. of paragraph 2.20.

Circulation areas and internal doorways

#

Source page 25

Door and hall widths

2.22To facilitate movement into, and between, rooms throughout the dwelling, doors and corridors should comply with all of the following (see Diagram 2.3).

a.The minimum clear width of every hall or landing is 900mm.

b.Any localised obstruction, such as a radiator, does not occur opposite or close to a doorway or at a change of direction and is no longer than 2m in length; and the corridor is not reduced below a minimum 750mm width at any point.

c.Every door has a minimum clear opening width as set out in Table 2.1.

d.A minimum 300mm nib is provided to the leading edge of every door within the entrance storey.

Plan diagram showing minimum door and hall widths, permitted and non-permitted obstruction zones, and dimensional requirements.
Diagram 2.3 Minimum door and hall widths and restrictions on localised obstructions
Table 2.1 Minimum widths of corridors and passageways for a range of doorway widths
Doorway clear opening width (mm)Corridor clear passageway width
750 or wider900 (when approached head on)
7501200 (when approach is not head-on)
7751050 (when approach is not head-on)
800900 (when approach is not head-on)

Private stairs and changes of level within the dwelling

#

Source page 26

Private stairs and changes of level within the dwelling

2.23To allow people to move between storeys, and to allow a stair-lift to be fitted to the stairs from the entrance storey to the storey above (or the storey below where this contains the bathroom required by the provisions of paragraph 2.29), stairs should comply with all of the following.

a.Access to all rooms and facilities within the entrance storey is step-free.

b.Level changes within every other storey are avoided where possible.

c.The stair from the entrance storey to the storey above (or below) has a minimum clear width of 850mm when measured 450mm above the pitch line of the treads (ignoring any newel post).

d.All stairs meet the provisions of Part K for private stairs.

Habitable rooms

Living, kitchen and eating areas

2.24To provide usable living spaces and easy, step-free access between a living area, a WC and the principal private entrance, key accommodation should comply with all of the following.

a.Within the entrance storey there is a living area (which may be a living room, dining room or a combined kitchen and dining room).

b.A minimum 1200mm clear space is provided in front of and between all kitchen units and appliances.

c.Glazing to the principal window of the principal living area starts a maximum of 850mm above floor level or at the minimum height necessary to comply with the requirements of Part K for guarding to windows.

Bedrooms

2.25To enable a wide range of people to access and use them, bedrooms should comply with all of the following.

a.Every bedroom can provide a clear access route a minimum 750mm wide from the doorway to the window.

b.At least one double bedroom (the principal bedroom) can provide a clear access zone a minimum 750mm wide to both sides and the foot of the bed.

c.Every other double bedroom can provide a clear access zone a minimum 750mm wide to one side and the foot of the bed.

d.All single and twin bedrooms can provide a clear access zone a minimum 750mm wide to one side of each bed.

e.It can be demonstrated (for example by providing dimensioned bedroom layouts, similar to the example in Diagram 2.4) that the provisions above can be achieved.

Sanitary facilities

#

Source page 27

Bedroom plan diagram showing a bed, furniture, door, window access, clear access zones marked a, and 600mm and 750mm dimensions, with notes.
Diagram 2.4 Clear access zones to principal bedroom

Sanitary facilities

General provisions

2.26All walls, ducts and boxings to the WC/cloakroom, bathroom and shower room should be strong enough to support grab rails, seats and other adaptations that could impose a load of up to 1.5kN/m². Additional sanitary facilities beyond those required to comply with this guidance need not have strengthened walls.

WC facilities on the entrance storey

2.27To provide step-free access to a WC that is suitable and convenient for some wheelchair users and, where reasonable, to make provision for showering, dwellings should comply with all of the following.

a.Every dwelling has a room within the entrance storey that provides a WC and basin (which may be within a WC/cloakroom or a bathroom).

b.In a two or three storey dwelling with one or two bedrooms, the WC (together with its associated clear access zone) meets the provisions of Diagram 1.3 and the basin does not impede access to the WC.

c.In a two or three storey dwelling with three or more bedrooms, the room with the WC and basin also provides an installed level access shower or a potential level access shower, and the shower, WC and basin (together with their associated clear access zones) meet the provisions of Diagram 2.5. Examples of compliant WC layouts are shown in Diagram 2.6.

d.The door opens outwards.

Page 28

#

Source page 28

Diagram showing sanitary fittings, clear access zones, permitted basin encroachments, dimensions and a 1500mm diameter clear turning circle.
Diagram 2.5 Sanitary fittings, associated clear access zones and permitted encroachment of basins

Notes:1. Sizes of fittings are minima based on the furniture schedule in Appendix D. Other larger sizes may affect the overall size of a bathroom or WC/cloakroom.

2.Access zones may overlap except where noted.

3.The access zone to the basin may extend under it as far as any fixed obstruction, such as a vanity unit, pedestal or trap.

4.In WC/cloakrooms the basin and/or WC may encroach into the shower space but this should be minimised.

5.Any radiator or towel rail should be clear of all access zones.

Bathrooms

#

Source page 29

Two example WC/cloakroom layouts, labelled Example 2.6A and Example 2.6B, with dimensions, access zones and outward-opening doors.
Diagram 2.6 Examples of WC/cloakroom layouts

Notes:1. Dimensions for illustration purposes only.

2.Doors should open outwards.

3.Stack and drainage positions to be shown clear of access zones where located within WC / Cloakroom.

2.28Where the dwelling provides both an accessible bathroom with a WC and a WC/cloakroom within the same storey, the WC/cloakroom may comply with the provisions of Diagram 1.3.

Bathrooms

2.29To provide convenient access to a suitable bathroom, the dwelling should comply with all of the following.

a.Every dwelling has a bathroom that contains a WC, a basin and a bath, that is located on the same floor as the double bedroom, described as the principal bedroom in paragraph 2.25b.

b.The WC, basin and bath (together with their associated clear access zones) meet the provisions of Diagram 2.5. Examples of bathroom layouts are shown in Diagram 2.7.

c.Provision for a potential level access shower is made within the bathroom if not provided elsewhere within the dwelling.

Services and controls

#

Source page 30

Two example Category 2 bathroom layouts, labelled Example 2.7A and Example 2.7B, showing fittings, access zones, dimensions and door positions.
Diagram 2.7 Examples of Category 2 bathrooms

Notes:1. Dimensions for illustration purposes only.

2.Stack and drainage positions to be shown clear of access zones where located within WC / Cloakroom.

3.Alternative door positions shown dotted.

Services and controls

2.30To assist people who have reduced reach, services and controls should comply with all of the following.

a.Consumer units are mounted so that the switches are between 1350mm and 1450mm above floor level.

b.Switches, sockets, stopcocks and controls have their centre line between 450mm and 1200mm above floor level and a minimum of 300mm (measured horizontally) from an inside corner.

c.The handle to at least one window in the principal living area is located between 450mm and 1200mm above floor level, unless the window is fitted with a remote opening device that is within this height range.

d.Handles to all other windows are located between 450mm and 1400mm above floor level, unless fitted with a remote opening device that is within this height range.

e.Either:

boiler timer controls and thermostats are mounted between 900mm and 1200mm above finished floor level on the boiler, or

separate controllers (wired or wireless) are mounted elsewhere in an accessible location within the same height range.

Optional requirement M4(3): Category 3 – Wheelchair user dwellings

#

Source page 31

This section of the approved document deals with the following optional requirement from Part M of Schedule 1 to the Building Regulations 2010.

Requirement
Optional requirementLimits on application
Category 3 – wheelchair user dwellings M4(3) optional requirement (1) Reasonable provision must be made for people to— (a) gain access to, and (b) use, the dwelling and its facilities. (2) The provision made must be sufficient to— (a) allow simple adaptation of the dwelling to meet the needs of occupants who use wheelchairs; or (b) meet the needs of occupants who use wheelchairs.Optional requirement M4(3)— (a) may apply only in relation to a dwelling that is erected; (b) will apply in substitution for requirement M4(1); (c) does not apply where optional requirement M4(2) applies; (d) does not apply to any part of a building that is used solely to enable the building or any service or fitting in the building to be inspected, repaired or maintained. Optional requirement M4(3) (2)(b) applies only where the planning permission under which the building work is carried out specifies that it shall be complied with.

Performance

In the Secretary of State’s view, optional requirement M4(3) will be met where a new dwelling makes reasonable provision, either at completion or at a point following completion, for a wheelchair user to live in the dwelling and use any associated private outdoor space, parking and communal facilities that may be provided for the use of the occupants. Reasonable provision is made if the dwelling complies with all of the following.

a.Within the curtilage of the dwelling or of the building containing the dwelling, a wheelchair user can approach and gain step-free access to every private entrance to the dwelling and to every associated private outdoor space, parking space and communal facility for occupants’ use.

b.Access to the WC and other accommodation within the entrance storey is step-free and the dwelling is designed to have the potential for step-free access to all other parts.

c.There is sufficient internal space to make accommodation within the dwelling suitable for a wheelchair user.

d.The dwelling is wheelchair adaptable such that key parts of the accommodation, including sanitary facilities and kitchens, could be easily altered to meet the needs of a wheelchair user or, where required by a local planning authority, the dwelling is wheelchair accessible.

e.Wall-mounted switches, controls and socket outlets are accessible to people who have reduced reach.

Section 3: Category 3 – Wheelchair user dwellings

#

Source page 32

Section 3A: Approach to the dwelling

Application

3.1The provisions of Section 3A apply only where a planning condition requires compliance with optional requirement M4(3) for a wheelchair user dwelling (see paragraphs 0.3 to 0.6).

3.2The provisions of Section 3A apply to specific external and internal areas and elements that form part of the approach route to the dwelling and fall within the plot (or curtilage) of the individual dwelling, or the building containing the dwelling.

3.3The provisions of Section 3A also apply to the approach route between the dwelling and the point, or points, at which a wheelchair user, or other disabled occupant or visitor, would expect to get in and out of a car. This point, or points, of access may be within or outside the plot of the dwelling, or the building containing the dwelling. These provisions do not apply beyond the curtilage of the development.

3.4Reasonable provision should also be made to ensure that the approach route to any communal facilities intended to serve the dwelling meets these provisions. Communal facilities include storage areas, such as those used for depositing refuse and recycling, but not plant rooms or other service areas unless occupants need regular access to equipment within these spaces, for example for meter reading.

3.5For a house (or other dwelling that sits within its own plot) the approach route will often only involve a driveway, or a gate and a path. For a dwelling within a larger building (typically a block of flats) the approach route usually involves one, or more, communal gates, paths, entrances, doors, lobbies, corridors and access decks, as well as communal lifts and stairs.

3.6All the provisions of Section 3A apply to wheelchair adaptable and wheelchair accessible dwellings.

Approach routes

General provisions

3.7The approach route should be safe and convenient for everyone, be at the shallowest gradient that can reasonably be achieved, and be step-free, irrespective of the storey on which the dwelling is located. Approach routes to dedicated storage for mobility scooters (where provided) should also be step-free.

3.8A step-free approach route should be provided to all private entrances. Where a communal ramped approach route is provided and has an overall rise of 300mm or more, an additional stepped route meeting the requirements of paragraph 3.11 should also be provided.

External and internal ramps forming part of an approach route

#

Source page 33

3.9An accessible step-free approach route that is specifically suitable for a wheelchair user should comply with all of the following.

a.The approach route is level, gently sloping or ramped.

b.The approach route (whether private or communal) has a minimum clear width of 1200mm.

c.Any localised obstruction does not occur opposite or close to a doorway or at a change of direction and is no longer than 2m in length.

d.A level space with a minimum width and depth of 1500mm for passing or turning is provided at each end of the approach route and at maximum intervals of 10m.

e.External parts of the approach route have a suitable ground surface.

f.External parts of the approach route are illuminated by fully diffused lighting activated automatically by a dusk to dawn timer or by detecting motion.

g.Every gate (or gateway) between the footway and the main communal or private entrance has all of the following:

a minimum clear opening width of 850mm

a minimum 300mm nib to the leading edge

a minimum 200mm nib to the following edge.

External and internal ramps forming part of an approach route

3.10External and internal ramps should comply with all of the following.

a.The gradient is between 1:20 and 1:15.

b.The length of each flight at a given gradient meets the provisions of Diagram 3.1.

c.Flights (whether within a private or communal approach route) have a minimum clear width of 1200mm.

d.Top and bottom landings are provided to every flight.

e.An intermediate landing is provided between individual flights and at any change of direction.

f.Every landing is level and a minimum of 1200mm clear of any door (or gate) swing.

External steps forming part of an additional route

#

Source page 34

Graph showing the maximum length of a ramp flight for gradients from 1:10 to 1:20, including rise values and compliant and non-compliant regions.
Diagram 3.1 Maximum length of ramp at a given gradient

Notes:1. Gradient x length of flight = rise e.g. 1/20 x 10 = 500mm.

External steps forming part of an additional route

3.11To enable a wide range of people to use them safely, external steps should comply with all of the following.

a.Steps are uniform with a rise of between 150mm and 170mm and a going of between 280mm and 425mm (for tapered steps measured at a point 270mm from the ‘inside’ (narrow end) of the step).

b.Steps have suitable tread nosings.

c.No individual flight has a rise of more than 1800mm between landings.

d.Every flight has a minimum clear width of 900mm.

e.Top, bottom and, where necessary, intermediate landings are provided and every landing is a minimum 900mm long.

f.Every flight with three or more risers has a suitable grippable handrail on one side of the flight (or to both sides where the flight is wider than 1000mm). This grippable handrail is 850-1000mm above the pitch line of the flight and extends at least 300mm beyond the top and bottom nosings.

g.Single steps are avoided.

Car parking and drop-off

#

Source page 35

Parking space

3.12Where a dwelling has a parking space, to enable a wheelchair user to get into and out of a car from both sides and access the boot space, the parking space should comply with all of the following.

a.Where the parking space is within the private curtilage of a dwelling (including a carport or garage) it is a standard parking bay with an additional minimum clear access zone of 1200mm to one side and to the rear.

b.Where it is within a communal parking area, it is a standard parking bay with an additional minimum clear access zone of 1200mm to both sides.

c.The parking space is level.

d.The parking space has a minimum clear headroom of 2200mm.

e.The parking space has a suitable ground surface.

Drop-off point

3.13Where a drop-off point (or setting down point) is provided for the dwelling, it should comply with all of the following.

a.The drop-off point is located close to the principal communal entrance of the core of the building that contains the dwelling.

b.The drop-off point is level.

c.The drop-off point has a suitable ground surface.

d.Where a dropped kerb is provided, it is a minimum of 1000mm wide, is reasonably flush with the adjoining ground and has a maximum gradient of 1:15.

Communal entrances

Principal communal entrance

3.14To enable a wheelchair user to enter the principal communal entrance, it should comply with all of the following.

a.There is a level landing with a minimum width and depth of 1500mm outside the entrance.

b.The landing is covered to a minimum width and depth of 1200mm.

c.Lighting is provided which uses fully diffused luminaires activated automatically by a dusk to dawn timer or by detecting motion.

d.A clear turning circle 1500mm in diameter is provided inside the entrance area, behind the entrance door when closed.

e.The entrance door (or gate) has a minimum clear opening width of 850mm when measured in accordance with Diagram 3.2.

f.Where double doors (or gates) are provided, the main leaf provides the required minimum clear opening width.

g.A minimum 300mm nib is provided to the leading edge of the door (or gate) and the extra width created by this nib is maintained for a minimum of 1800mm beyond it.

Other communal doors

#

Source page 36

h.A minimum 200mm nib is provided to the following edge of the door (or gate) and the extra width created by this nib is maintained for a distance of a minimum 1800mm beyond it.

i.The door is located reasonably centrally within the thickness of the wall while ensuring that the depth of the reveal on the leading face of the door (usually the inside) is a maximum of 200mm.

j.The threshold is an accessible threshold.

k.Where there is a lobby or porch, the doors are a minimum of 1500mm apart and there is a minimum of 1500mm clear space between door swings.

l.Power assisted opening is provided where the opening force of the door is more than 30N from 0° to 30° or more than 22.5N from 30° to 60° of the opening cycle.

m.The ground surface (or entrance flooring) does not impede movement by wheelchair users.

n.Door entry controls, where provided, are mounted 900-1000mm above finished ground level a minimum of 300mm away from any projecting corner.

Technical door plan diagram showing measurement of clear opening width, door edges, nibs, reveal depth, and associated key and notes.
Diagram 3.2 Measurement of clear opening width and other features of external and internal doors

Other communal doors

3.15Every communal door, or gate, along the approach route should comply with provisions e. to n. of paragraph 3.14.

Communal lifts and stairs

Communal lifts

3.16To enable a wide range of people, including accompanied wheelchair users, to access and use the lift, every communal passenger lift that gives access to the dwelling should comply with all of the following.

a.A clear landing, a minimum of 1500mm long and 1500mm wide, is directly in front of the lift door at every floor level.

Communal stairs

#

Source page 37

b.The lift is equivalent to or complies with requirements of BS EN 81-70:2003 for a type 2 lift.

c.The lift car is a minimum of 1100mm wide and 1400mm deep

d.Doors have a minimum clear opening width of 800mm.

e.Landing and car controls are located 900-1200mm above the car floor and a minimum of 400mm (measured horizontally) from the inside of the front wall.

f.The lift has an initial dwell time of five seconds before its doors begin to close after they are fully open.

Communal stairs

3.17The principal communal stair that gives access to the dwelling should meet the provisions of Part K for a general access stair.

Section 3B: Private entrances and spaces within, and connected to, the dwelling

#

Source page 38

Application

3.18The provisions of Section 3B apply only where a planning condition requires compliance with optional requirement M4(3) for a wheelchair user dwelling (see paragraphs 0.3 to 0.6).

3.19The provisions of Section 3B apply to private entrances, other external doors and key elements within the dwelling. They also cover any associated private outdoor space, garden, balcony or private roof terrace.

3.20In order to demonstrate that the dwelling is capable of meeting the functional and spatial provisions for a wheelchair adaptable or wheelchair accessible dwelling, furnished plan layouts that show the access zones and other provisions of Section 3B and the furniture of the furniture schedule included as Appendix D of this approved document should be provided to a scale of at least 1:100.

3.21All the provisions of Section 3B apply to wheelchair adaptable and wheelchair accessible dwellings, except where noted otherwise.

Private entrances

Principal private entrance

3.22The principal private entrance to the individual dwelling should comply with all of the following (see Diagram 3.3).

a.There is a level external landing with a minimum width and depth of 1500mm and clear of any door swing.

b.The landing area is covered for a minimum width and depth of 1200mm.

c.Lighting is provided which uses fully diffused luminaires activated automatically by a dusk to dawn timer or by detecting motion.

d.There is a minimum 1500mm clear turning circle inside the entrance area, in front of the door when closed.

e.A minimum 300mm nib is provided to the leading edge of the door and the extra width created by this nib is maintained for a minimum of 1800mm beyond it. A minimum 150mm nib is provided to the hinge side of the door (to allow for the fitting of a cage to the inside face of the letter box).

f.The door has a minimum clear opening width of 850mm, when measured in accordance with Diagram 3.2.

g.Where there are double doors, the main (or leading) leaf provides the required minimum clear opening width. A minimum 200mm nib is provided to the following edge of the door and the extra width created by the nib is maintained for a minimum of 1500mm beyond it.

Page 39

#

Source page 39

Technical access-route diagram showing a garden gate, private approach route, landing area, principal entrance door, thresholds, clearances, turning circle, canopy, and associated key labels.
Diagram 3.3 Features associated with principal private entrance

Other external doors

#

Source page 40

h.The door is located reasonably centrally within the thickness of the wall while ensuring that the depth of the reveal on the leading face of the door (usually the inside) is a maximum of 200mm.

i.The threshold is an accessible threshold.

j.Where there is a lobby or porch, the doors are a minimum of 1500mm apart and there is a minimum of 1500mm between door swings.

k.Door entry controls, where provided, are mounted 900-1000mm above finished ground level a minimum of 300mm away from any external return corner.

l.A fused spur, suitable for the fitting of a powered door opener, is provided on the hinge side of the door.

Other external doors

3.23All other external doors – including doors to and from a private garden, balcony, terrace, garage, carport, conservatory or storage area that is integral with, or connected, the dwelling comply with provisions f. to k. of paragraph 3.22 and should have a minimum 300mm nib to the leading edge of the door with the extra width created by this nib extending for a minimum 1800mm beyond it.

Circulation areas, internal doorways and storage

Hall and door widths

3.24To facilitate wheelchair movement into and between rooms, internal halls and doors should comply with all of the following (see Diagram 3.4).

a.The minimum clear width of every hallway, approach or landing is 1050mm.

b.Where the approach to a doorway is not head-on, the minimum clear width of the hallway or approach is 1200mm.

c.Any localised obstruction, such as a radiator, does not occur opposite or close to a doorway or at a change of direction and is no longer than 2m in length, as shown in Diagram 3.4.

d.Every door has a minimum clear opening width of 850mm, irrespective of the direction of entry, when measured in accordance with Diagram 3.2.

e.Where an outward opening door is located close to a corner and another door is located on the return wall within 800mm of that corner, the leading edge of the outward opening door is a minimum of 800mm from the corner, as shown in Diagram 3.5, unless a 1500mm turning circle is provided immediately outside the door.

f.A minimum 300mm nib is provided to the leading edge of every door.

g.A minimum 200mm nib is provided to the following edge of every door.

Wheelchair storage and transfer space

#

Source page 41

Plan diagram showing minimum door and hall widths, permitted and prohibited localised obstructions, and dimensional requirements.
Diagram 3.4 Minimum door and hall widths and restrictions on localised obstructions
Three plan diagrams showing outward-opening doors in a corner, with circulation areas and minimum dimensional requirements.
Diagram 3.5 Outward opening doors in a corner

Wheelchair storage and transfer space

3.25To enable a person to charge and store up to two wheelchairs and transfer between an outdoor and an indoor wheelchair, a dwelling should have a storage and transfer space which complies with all of the following.

a.A minimum 1100mm deep by 1700mm wide space is available on the entrance storey, preferably close to the principal private entrance.

b.Is accessible from a space that has a minimum clear width of 1200mm, as shown in Diagram 3.6.

c.A power socket is provided within the space.

General storage space

#

Source page 42

d.In wheelchair adaptable dwellings the storage and transfer space may be used for another purpose such as general storage (and doors fitted if required) provided that:

the provisions of paragraph 3.25 can be met without alteration to structure or services, and

the space is additional to the minimum requirements for storage, living spaces and bedrooms set out in paragraphs 3.26, 3.31 and 3.35.

Plan diagram showing wheelchair storage and transfer space with dimensions of 1100mm, 1200mm and 1700mm and a power socket.
Diagram 3.6 Wheelchair storage and transfer space

General storage space

3.26To make adequate provision for the storage of household items, general built-in storage space should comply with Table 3.1.

Table 3.1 Minimum area of general built-in storage
Number of bedrooms123456
Minimum storage area (m²)1.52.02.53.03.54.0

Through-floor lifting device provision

3.27To ensure that provision can be made for a wheelchair user to access to all parts of a dwelling on more than one floor level, the dwelling should comply with either the requirements of paragraph 3.28 for a wheelchair adaptable dwelling or 3.29 for a wheelchair accessible dwelling.

3.28Where the dwelling is defined as wheelchair adaptable, it should be easy to install a lift. The space for the liftway can, however, be used for another purpose (such as storage or part of a habitable room) providing it is demonstrated that the dwelling complies with all of the following.

a.Any floors, walls and doors that have been installed to allow the potential liftway to be used as storage or for other purposes could be easily removed without structural alteration.

Page 43

#

Source page 43

b.Future provision for the liftway is a minimum of 1100mm wide and 1650mm long internally linking circulation areas at every floor level of the dwelling.

c.Where walls forming the liftway enclosure are not initially installed, they can be easily reinstated without the need for structural works and would not compromise compliance with this or any other part of the Building Regulations.

d.Drawings demonstrate how all the provisions of paragraph 3.29 can be complied with if a suitable lifting device is fitted in the future.

e.The space for the future lift installation is not used to meet other requirements and in particular is not included in the minimum living, kitchen and eating area set out in paragraph 3.31.

3.29Where the dwelling is defined as wheelchair accessible, a suitable through-floor lift or lifting platform should be installed and commissioned and the dwelling should comply with all of the following.

a.There is a continuous liftway a minimum 1100mm wide and 1650mm long internally linking every floor level of the dwelling.

b.The liftway can be entered from the same one of its narrower ends at every floor level.

c.A minimum 1500mm clear turning circle, clear of the liftway door when open at 90 degrees, could be provided in front of the liftway door at every floor level, as shown in Diagram 3.7.

d.A power socket, suitable for powering the lifting device, is provided close to the liftway.

e.The shaft is positioned to allow the lift to run between the circulation areas in every storey of the dwelling (irrespective of the number of storeys).

f.Lifting devices should be positioned with the end opposite to the entry point located against a wall at every floor level.

g.Doors are power operated.

Plan diagram showing a through-floor lift or future lift space, circulation area, a 1500mm clear turning circle, 1650mm liftway length, 1100mm width, power-operated doors, and notes about clearance from adjacent steps.
Diagram 3.7 Access to through floor lift

Private stairs and changes of level within the dwelling

#

Source page 44

3.30An ambulant disabled person should be able to move within, and between, storeys. It should also be possible to fit a stair-lift to the stairs from the entrance storey to the storey above (or the storey below where this contains the bathroom required by the provisions of paragraph 3.41). The dwelling should comply with all of the following.

a.Access to all rooms and facilities within the entrance storey is step-free.

b.There are no changes of level within any other storey.

c.The stair from the entrance storey to the storey above (or below) and any stair within the storey above (or below) has a minimum clear width of 850mm when measured at 450mm above the pitch line of the treads (ignoring any newel post).

d.A power socket suitable for powering a stair-lift is provided close to the foot or head of any stair to which a stair lift may be fitted.

e.All stairs meet the provisions of Part K for private stairs.

Habitable rooms

Living areas

3.31To provide usable living spaces that have a convenient, step-free relationship between the living space, WC and principal private entrance, living areas should comply with all of the following.

a.The principal living area is within the entrance storey.

b.The minimum combined internal floor area of living, dining and kitchen space meets the provisions of Table 3.2.

c.Glazing to the principal window of this living area starts a maximum of 850mm above floor level or at the minimum height reasonable in achieving compliance with the provisions of Part K for guarding to windows.

Table 3.2 Minimum combined floor area for living, dining, and kitchen space
Number of bedspaces2345678
Minimum floor area m²25272931333537

Kitchen and eating areas

3.32The relationship between the kitchen, dining and living areas should be convenient and step-free. Kitchen and eating areas should comply with all of the following.

a.The kitchen and principal eating area are within the same room, or connected to each other, and located within the entrance storey.

b.There is a minimum clear access zone 1500mm wide in front of, and between, all kitchen units and appliances.

3.33Where the dwelling is defined as wheelchair adaptable, in addition to the provisions of paragraph 3.32, the kitchen should comply with all of the following.

a.The overall length of kitchen worktop meets at least the provisions of Table 3.3.

Page 45

#

Source page 45

b.Drawings demonstrate how the kitchen could be easily adapted to meet the provisions of paragraph 3.34 and Table 3.4 at a future date without compromising the space in any other part of the dwelling and without the need to move structural walls, stacks or concealed drainage.

Table 3.3 Minimum length of kitchen worktop, including fittings and appliances, to be fitted at completion for a wheelchair adaptable dwelling
Number of bedspaces23 & 456–8
Minimum worktop length (mm)4330473056306730
Technical kitchen layout diagram showing wheelchair accessible worktop, sink, hob, appliances, storage units, dimensions, access arrangements and explanatory notes.
Diagram 3.8 Example of a wheelchair accessible kitchen layout

Bedrooms

#

Source page 46

3.34Where the dwelling is defined as wheelchair accessible, in addition to the provisions of paragraph 3.32, the kitchen should comply with all of the following (see in Diagram 3.8).

a.The overall length of kitchen worktop meets the provisions of Table 3.4.

b.The worktop includes a continuous section that incorporates a combined sink and drainer unit and a hob, and all of the following.

The section of worktop is a minimum 2200mm long.

The section of worktop is either a height adjustable worktop, or is a fixed section capable of being refixed at alternate heights.

There are no fixed white goods (appliances) placed beneath this section of worktop.

This section of worktop provides clear and continuous open leg space underneath (capable of achieving a minimum of 700mm clearance above floor level).

c.The sink is not more than 150mm deep with insulation to the underside to prevent scalding of a wheelchair user’s legs.

d.Taps should be lever operated and capable of easy operation.

e.A suitable space has been identified for a built-in oven (with its centre line between 800mm and 900mm above floor level) to be installed.

f.A pull out shelf is provided beneath the oven enclosure.

g.There is a minimum of 400mm of worktop to at least one side of the oven and fridge or fridge freezer where this is taller than the worktop height (or to one side of a pair of tall appliances where they are located together at the end of a run).

h.Water supply to sinks includes isolation valves and flexible tails.

i.Drainage is either flexible, or is fixed but easily adaptable to suit worktop heights between 700mm and 950mm above finished floor level.

Table 3.4 Minimum length of kitchen worktop, including fittings and appliances, to be fitted at completion for a wheelchair accessible dwelling
Number of bedspaces23 & 456–8
Minimum worktop length (mm)6130653074308530

Bedrooms

3.35One bedroom should be close to an accessible bathroom suitable for a wheelchair user. All other bedrooms should be accessible to a wheelchair user. Bedrooms should comply with all of the following.

a.Every bedroom can provide a minimum clear access route, 750mm wide, from the doorway to the window.

b.Every bedroom can provide a minimum 1200mm by 1200mm manoeuvring space inside the doorway, clear of the bed and the door (when the door is in the closed position).

c.The ceiling structure to every bedroom is strong enough to allow for the fitting of an overhead hoist capable of carrying a load of 200kg.

Page 47

#

Source page 47

d.A principal double bedroom is located on the entrance storey, or the storey above (or below) the entrance storey, has a minimum floor area of 13.5m² and is a minimum of 3m wide clear of obstructions (e.g. radiators).

e.The principal double bedroom can provide a minimum 1000mm wide clear access zone to both sides and the foot of the bed and in front of all furniture, and a minimum 1200mm by 1200mm manoeuvring space on both sides of the bed (see Diagram 3.9).

f.Every other double (or twin) bedroom has a minimum floor area of 12.5m² and is a minimum of 3m wide.

g.Every other double bedroom can provide a 1000mm wide clear access zone to one side and the foot of the bed, and in front of all furniture.

h.All single and twin bedrooms provide a minimum 1000mm clear access zone to one side of each bed and in front of all furniture.

i.Every single bedroom has a minimum floor area of 8.5m² and is at least 2.4m wide.

Technical bedroom layout diagram showing a bed, furniture, clear access zones, manoeuvring spaces, dimensions and explanatory notes.
Diagram 3.9 Clear access zones and manoeuvering spaces to principal bedroom

Sanitary facilities

#

Source page 48

General provisions

3.36Dwellings should provide suitable WC and washing facilities. Reasonable provision will vary depending on whether dwellings are wheelchair adaptable or wheelchair accessible. To provide suitable and convenient sanitary facilities, a dwelling should comply with all of the following.

a.WC facilities are provided which comply with the relevant requirements of paragraphs 3.37 to 3.40, and bathroom facilities are provided which comply with the relevant requirements of paragraphs 3.41 to 3.43.

b.Any dwelling with four or more bedspaces provides access to a minimum of two WCs in separate bathrooms or WC/cloakrooms (see Table 3.5).

c.Every room that contains an installed level access shower is constructed as a wet room.

d.All walls, ducts and boxings to every WC/cloakroom, bath and shower room are strong enough to support grab rails, seats and other adaptations that could impose a load of 1.5kN/m².

e.The ceiling structure to bathrooms and WC/cloakrooms required by paragraphs 3.36 to 3.40 is strong enough to allow for the fitting of an overhead hoist capable of carrying a load of 200kg.

f.Where sanitary facilities are wheelchair accessible, WC flush controls are positioned on the front of the cistern on the transfer side and can be easily gripped, e.g. a lever flush handle.

g.Where sanitary facilities are wheelchair accessible, WC pans should be a minimum of 400mm high.

h.Where sanitary facilities are wheelchair accessible, basins and sinks should be wall hung (typically with their rim 770-850mm above finished floor level) and the clear zone beneath basins, services and pedestals is maximised to enable wheelchair users to approach. Ideally this clear zone should be in the range 400-600mm from finished floor level.

i.Stacks or soil and vent pipes should only be positioned adjacent to WC where there is no practical alternative and should always be on the wall side of the WC.

WC facilities on the entrance storey

#

Source page 49

**Table 3.5** **Summary of minimum requirements for sanitary provision in typical dwelling types** (dwellings should also comply with relevant detailed requirements set out in paragraphs 3.36–3.43)
OccupancyTypical minimum sanitary provision
Single storey dwelling (typically a flat or bungalow)
2 or 3 bedspacesBathroom with level access shower
4 bedspacesBathroom with level access shower and separate WC/cloakroom
5 bedspaces or moreBathroom with level access shower and separate WC/cloakroom (or second bathroom). Wheelchair accessible dwellings must also provide both a level access shower and a bath
Two or three storey dwelling (typically a house or maisonette)
2 or 3 bedspacesBathroom with level access shower on same level as principal bedroom + entrance storey WC/cloakroom (where bathroom not on the entrance storey)
4 bedspacesBathroom with level access shower on same level as principal bedroom and entrance storey WC/cloakroom or second bathroom
5 bedspaces or moreBathroom with level access shower on same level as principal bedroom and entrance storey WC/cloakroom or second bathroom. Wheelchair accessible dwellings must also provide both a level access shower and a bath

WC facilities on the entrance storey

3.37To make suitable and convenient provision for a wheelchair user to use a WC, the dwelling should comply with all of the following.

a.Every dwelling has, on the entrance storey, a wet room (which may be a WC/cloakroom or a bathroom) that contains a WC, a basin and an installed level access shower and complies with the requirements of either paragraph 3.38 or 3.39.

b.Where the dwelling provides both a bathroom and a WC/cloakroom on the same storey, the WC facility need only comply with the requirements of paragraph 3.40.

c.The door to the WC facility opens outwards.

3.38Where the dwelling is defined as wheelchair adaptable, WC facilities should also comply with all of the following.

a.The WC, basin and shower (and their associated clear access zones) meet the provisions in Diagram 3.10. An example of a compliant design is shown in Diagram 3.12.

b.It is demonstrated how the WC/cloakroom could be easily adapted in future to meet the provisions of paragraph 3.39.

Page 50

#

Source page 50

Technical bathroom and WC layout diagrams showing sanitary fittings, clear access zones, permitted basin encroachment, dimensions, turning circle and explanatory notes.
Diagram 3.10 Sanitary fittings associated clear access zones and permitted encroachment of basins – wheelchair adaptable

Page 51

#

Source page 51

3.39Where the dwelling is defined as wheelchair accessible, WC facilities should also comply with all of the following.

a.The WC, basin and shower (and their associated clear access zones) meet the provisions in Diagram 3.11. Examples of compliant designs are shown in Diagram 3.12.

Technical bathroom and WC layout diagrams showing sanitary fittings, clear access zones, grab-rail zone, permitted encroachment, turning circle, shower arrangements, dimensions and explanatory notes.
Diagram 3.11 Sanitary fittings, associated clear access zones and permitted encroachment of basins – wheelchair accessible

Page 52

#

Source page 52

Two floor-plan examples showing wheelchair adaptable and wheelchair accessible WC/cloakroom layouts, with dimensions and access zones.
Diagram 3.12 Example of wheelchair adaptable WC/cloakroom layout with potential to be wheelchair accessible

Page 53

#

Source page 53

3.40Where the dwelling provides both a bathroom and a WC/cloakroom on the same storey, the WC and basin in the WC/cloakroom (and their associated clear access zones) should as a minimum comply with the provisions shown in Diagram 3.13. Examples of compliant designs are shown in Diagram 3.14.

Diagram showing sanitary fittings, clear access zones, permitted basin locations and encroachment zones for a second WC or cloakroom.
Diagram 3.13 Sanitary fittings, associated access zones and permitted encroachment of basis for second WC/cloakroom where on same floor level as first WC
Two floor-plan examples of compliant second WC or cloakrooms on the same floor level as the first WC.
Diagram 3.14 Examples of compliant second WC/cloakrooms where on the same floor level as the first WC

Bathroom facilities

#

Source page 54

3.41To make suitable and convenient provision for a wheelchair user to bathe or use a wheelchair accessible shower, with assistance where necessary, the dwelling should comply with all of the following.

a.Dwellings with up to four bedspaces should have as a minimum a bathroom that contains a WC, a basin and an installed level access shower with the potential for a bath to be installed above it (unless a bath is provided in addition to the installed level access shower within this bathroom or elsewhere on the same storey).

b.The bathroom containing the installed level access shower should be located on the same storey as the principal double bedroom described in paragraph 3.35.

3.42Where the dwelling is defined as wheelchair adaptable, it is assumed that most commonly a bath will be installed over a useable level access shower, though this is not a requirement. Wheelchair adaptable bathrooms should also comply with all of the following.

a.The WC, basin, bath and shower (and their associated clear access zones) meet at least the provisions shown in Diagram 3.10. Examples of compliant designs are shown in Diagram 3.15.

b.Drawings illustrate how the bathroom could be easily adapted in future to meet the provisions for a wheelchair accessible bathroom set out in paragraph 3.43 (but need only show either a bath or level access shower, not both).

3.43Where the dwelling is defined as wheelchair accessible, the bathroom should also comply with all of the following.

a.The WC, basin, bath (where provided) and shower (and their associated clear access zones), meet the provisions in Diagram 3.11. Examples of compliant designs are shown in Diagram 3.16.

b.In dwellings with up to four bedspaces, an installed level access shower is provided as the default but a bath can be accommodated as an alternative if required.

c.In dwellings with five bedspaces or more, both a useable bath and an installed level access shower are provided (either in one bathroom or in more than one bathroom on the same storey as the principal bedroom). Examples of bathrooms with shower and bath are provided in Diagram 3.17.

d.The level access shower is positioned in a corner to enable a shower seat to be fitted on one wall, with shower controls fitted on the adjacent wall.

e.The bathroom (or bathrooms) provides a minimum 1500mm clear turning circle.

Page 55

#

Source page 55

Two floor-plan examples showing wheelchair adaptable bathroom layouts with bath, WC, basin, access zones and outward-opening doors.
Diagram 3.15 Examples of wheelchair adaptable bathroom layouts with potential to be wheelchair accessible

Page 56

#

Source page 56

Three floor-plan examples of wheelchair accessible bathrooms: two with a choice of bath or shower and one with a shower only, showing dimensions, access zones and zones kept clear for fitting rails.
Diagram 3.16 Examples of wheelchair accessible bathrooms

Services and controls

#

Source page 57

Two annotated floor-plan diagrams showing wheelchair accessible bathrooms with baths and showers, including dimensions, access zones, fixtures and door swings.
Diagram 3.17 Examples of wheelchair accessible bathrooms with both bath and shower

Services and controls

3.44To assist wheelchair users who have reduced reach, services and controls should comply with all of the following.

a.Consumer units should be mounted so that the switches are between 1350mm and 1450mm above floor level.

b.Switches, sockets, stopcocks and controls, except controls to radiators, are located with their centre line 700-1000mm above floor level and a minimum of 700mm (measured horizontally) from an inside corner, and are not positioned behind appliances.

Private outdoor space

#

Source page 58

c.Kitchen appliances in wheelchair accessible dwellings have isolators located within the same height range.

d.The handle to at least one window in the principal living area is 700-1000mm above floor level, unless fitted with a remote opening device that is within this height range.

e.Handles to all other windows are 450-1200mm above floor level, unless the window is fitted with a remote opening device that is within this height range.

f.Door handles, locks, latches and catches are both:

easy to grip and use, and

fitted 850-1000mm above floor level.

g.Light switches are on individual plates unless wide rocker or full plate fittings are provided.

h.Switches to double socket outlets are located at the outer ends of the plate (rather than in the centre).

i.A door entry phone with remote door release facility is provided in the main living space and the principal bedroom.

j.Suitable provision is made in the principal bedroom to install bedhead controls in the future (comprising a 2-way light switch, telephone and broadband socket, TV aerial and power socket outlets, and the door entry phone provision described above, grouped adjacent to the head of the bed), for example, by providing blank sockets, conduit and draw wires.

k.A main electrical power socket and a telephone point are provided together in the main living space.

l.Taps and bathroom controls are suitable for a person with limited grip to operate and for single handed operation.

m.Boiler timer controls and thermostats are either mounted 900-1200mm above finished floor level on the boiler, or separate controllers (wired or wireless) are mounted elsewhere in an accessible location within the same height range.

n.In wheelchair accessible dwellings, radiator controls are mounted 450-1000mm above floor level.

Private outdoor space

3.45To enable a wheelchair user to use every private outdoor space that is provided, whether a private garden, balcony or roof terrace, outdoor space should comply with all of the following.

a.Every outdoor space both:

has a minimum clear width of 1500mm, and

provides a minimum 1500mm level clear turning circle, free of any door swing.

b.There is a level or gently sloping path with a minimum clear width of 1050mm to every private refuse, recycling, cycle or other external store.

c.Every path terminates in a clear turning circle a minimum of 1500mm in diameter.

d.Every gate (or gateway) has a minimum clear opening width of 850mm, a minimum 300mm nib to the leading edge and a minimum 200mm nib to the following edge.

e.The door to every private external store that is integral with, or connected to, the dwelling has a minimum clear opening width of 850mm.

f.All paved areas have a suitable ground surface.

Appendix A: Key terms

#

Source page 59

The following are key terms used in this document:

Note: Terms shown with * are defined in legislation, either in the Building Act 1984 or the Building Regulations 2010, where the definition may be fuller than the definition given here.

Accessible threshold

A threshold that is level or, if raised, has a total height of not more than 15mm, a minimum number of upstands and slopes and with any upstands higher than 5mm chamfered. Other acceptable solutions are described in Accessible thresholds in new housing – Guidance for house builders and developers, The Stationery Office Ltd. ISBN 0 11 702333 3. 1999.

Approach route

Internal or external path or corridor usually leading to the principal private entrance of a dwelling from a defined starting point (typically the pavement immediately outside of the curtilage or plot boundary).

Bedspace

A suitable sleeping area for one person. (A single bedroom provides one bedspace and a double or twin bedroom provides two bedspaces where these rooms also meet any other requirements for the relevant category of dwelling).

Clear access route

Clear, unobstructed ‘pathway’ to access a window or other feature. Localised obstructions are not permitted unless specifically stated.

Clear access zone

Clear, unobstructed space for access or manoeuvring. Localised obstructions are not permitted unless specifically stated.

Clear opening width

Clear distance measured between the inside face of the doorframe (or door stop) and the face of the door when open at 90 degrees. Door furniture and ironmongery may be disregarded when measuring the clear opening width.

Clear turning circle

Clear floor space, represented by a circle, or an ellipse, that allows a wheelchair user to turn independently in a single movement. A door swing is permitted within a clear turning space unless stated otherwise.

Clear width

Clear distance measured between walls or other fixed obstructions (except permitted localised obstructions) or across a path. Skirtings totalling up to 50mm total thickness and shallow projecting ducts or casings above 1800mm may be discounted when measuring clear width.

Communal or common (area, facilities or entrances)

Shared area accessed by, or intended for the use of, more than one dwelling.

Dwelling*

A house or flat. Student accommodation is treated as hotel/motel accommodation.

Entrance storey

The floor level (of the dwelling) on which the principal private entrance is located.

Flat*

Separate and self-contained premises constructed or adapted for residential purposes and forming part of a building from which it is divided horizontally.

Following edge (of door)

#

Source page 60

The surface of a door which follows into (or faces away from) the room or space into which the door is being opened – sometimes referred to as ‘the push side’.

Gently sloping

Gradient between 1:60 and 1:20

Habitable room

A room used, or intended to be used, for dwelling purposes, including a kitchen but not a bathroom or utility room.

Installed level access shower

Step-free area with no lips or upstands, suitable for showering, with a floor laid to shallow falls towards a floor gulley connected to the drainage system.

Leading edge (of door)

The surface of a door which leads into (or faces) the room or space into which the door is being opened – sometimes referred to as ‘the pull side’.

Level

Gradient not exceeding 1:60

Liftway

Vertical route linking all floors of a dwelling accommodating (or capable of accommodating) a lift or lifting platform.

Localised obstruction

Short, fixed element, such as a bollard lighting column or radiator, not more than 150mm deep that may intrude into a path, route, or corridor, that does not unduly restrict the passage of a wheelchair user.

Manoeuvring space

Clear floor space, represented by a rectangle which allows a wheelchair user to turn independently in a series of manoeuvres. A door swing is permitted within a clear manoeuvring space unless stated otherwise

Pitch line

A line that connects the nosing of the treads of a stair.

Plot gradient

The gradient measured between the entrance storey finished floor level of the dwelling and the point of access.

Point of access

The point at which a person visiting a dwelling would normally get out of a car before approaching the dwelling. The point of access may be within or outside the plot.

Potential level access shower

Space capable of providing a level access shower without the need to move walls, remove screed or other solid flooring. It should include a capped-off floor gulley, set at an appropriate level and connected to the drainage system. (Usually provided within a wet room).

Principal communal entrance

The communal entrance (to the core of the building containing the dwelling) which a visitor not familiar with the building would normally expect to approach (usually the common entrance to the core of a block of flats).

Principal private entrance

The entrance to the individual dwelling that a visitor not familiar with the dwelling would normally approach (usually the ‘front door’ to a house or ground floor flat).

Principal storey

The floor level (of the dwelling) on which the main living space is located, where this is not the entrance storey.

Private (area, facilities or entrances)

Area belonging to an individual dwelling.

Ramped

Gradient between 1:20 and 1:12

Standard parking bay

#

Source page 61

A parking bay 2.4m wide x 4.8m long

Steeply sloping plot

A plot where the gradient exceeds 1:15.

Step-free

Route without steps but that may include a ramp or a lift suitable for a wheelchair user.

Suitable ground surface

External ground surface that is firm, even, smooth enough to be wheeled over, is not covered with loose laid materials such as gravel and shingle, and has a maximum crossfall of 1:40.

Suitable tread nosings

Nosings that conform with one of the options shown in Diagram 1.2 of Approved Document K.

Wheelchair accessible

Category 3 dwelling constructed to be suitable for immediate occupation by a wheelchair user where the planning authority specifies that optional requirement M4(3)(2)(b) applies.

Wheelchair adaptable

Category 3 dwelling constructed with the potential to be adapted for occupation by a wheelchair user where optional requirement M4(3)(2)(a) applies.

Wet room

WC or bathroom compartment with tanking and drainage laid to fall to a connected gulley capable of draining the floor area when used as a shower.

Appendix B: Standards referred to

#

Source page 62

BS EN 81-70

Safety rules for the construction and installation of lifts. Particular applications for passenger and goods passenger lifts. Accessibility to lifts for persons including persons with disability [2003]

BS 5900

Powered home-lifts with partially enclosed carriers and no liftway enclosures. Specification [2012]

Appendix C: Other documents referred to

#

Source page 63

Legislation

Building Regulations 2010 (SI 2010/2214)(as amended)

Equality Act 2010 (2010 c.15)

Equality Act 2010 (Disability) Regulations (SI 2010/2128)

The Workplace (Health, Safety and Welfare) Regulations (SI 1992/3004)(as amended).

Other documents

Accessible thresholds in new housing – Guidance for house builders and developers, The Stationery Office Ltd. ISBN 0 11 702333 3. 1999.

Appendix D: Furniture schedule

#

Source page 64

SpaceFurniture to be shownFurniture size (mm)2345678
Living spaceArm chair (or number sofa seats in addition to minimum sofa provision)850x8502312341
2 seat settee (optional)850x1300
3 seat settee850x18501111
TV220x6501111111
coffee table500x1050 or 750 diameter
occasional table450x450
storage units500 x length shown (1 only required)100010001500200020002000
Dining spacedining chair234567+
dining table800 x length shown (1 only required)80010001200135015001650
Bedrooms
Double BedroomPrincipal bedroom double bed; or2000x15001111111
Other double bedroom double bed; or1900x13501111111
single bed (2 number in twin)1900x9002222222
bedside table400x4002222222
desk and chair500x10501111111
chest of drawers450x7501111111
double wardrobe600x12001111111
Twin bedroomsingle bed (2 number in twin)1900x90022222
bedside table400x40022222
chest of drawers450x75011111
table and chair500x105011111
double wardrobe600x120011111
Single Bedroomsingle bed1900x900111111
bedside table400x400111111
chest of drawers450x750111111
table and chair500x1050111111
double wardrobe600x1200111111
BathroomsWC + cistern500x700
Bath700x1700
Wash hand basin600x450
Hand rinse basin350x200
Manoeuvring zone
BedroomsManoeuvring square as per requirements1200x1200
Living roomsTurning circle; or1500x1500
Turning ellipse1400x1700

Index

#

Source page 65

Note: Category 1 – Visitable dwellings Category 2 – Accessible and adaptable dwellings Category 3 – Wheelchair user dwellings

A

accessible and adaptable dwellings 2.1–2.30

access zones bathrooms 2.29, 3.42, 3.43; Diagrams 2.5, 2.7, 3.15–3.17 bedrooms 2.25, 3.35; Diagrams 2.4, 3.9 kitchens 3.32 parking spaces 2.12, 3.12 sanitary fittings Diagrams 2.5, 3.10, 3.11 WC facilities 2.27, 3.38–3.40; Diagrams 1.3, 3.10, 3.11, 3.13

approach route optional requirement 0.4 Category 1 1.1–1.8 Category 2 2.1–2.11 Category 3 3.1–3.10

B

basins permitted encroachment Diagrams 2.5, 3.10, 3.11 wheelchair accessible dwellings 3.36

bathrooms Category 2 2.29; Diagram 2.7 Category 3 3.41–3.43; Diagrams 3.10, 3.11 wheelchair accessible 3.43; Diagrams 3.16, 3.17 wheelchair adaptable 3.42; Diagram 3.15

bedrooms Category 2 2.25 Category 3 3.35 clear access zones Diagrams 2.4, 3.9

British Standards BS EN 81-70 1.11, 2.16, 3.16 BS 5900 3.29

Building Regulations 2010 Part C 0.15 Part K 0.14

C

car parking Category 2 2.12 Category 3 3.12

circulation areas 1.15, 2.22, 3.24

clear opening width Diagrams 1.1, 2.2, 3.2

cloakrooms see WC facilities

communal entrances Category 1 1.9; Diagram 1.1 Category 2 2.14; Diagram 2.2 Category 3 3.14; Diagram 2.2

communal lifts Category 1 1.10, 1.11 Category 2 2.16 Category 3 3.16

communal stairs 1.10, 1.12, 2.17, 3.17

controls 1.18, 2.30, 3.44; Diagram 1.5

corridors Category 1 1.15; Table 1.1; Diagram 1.2 Category 2 2.22; Table 2.1; Diagram 2.3 Category 3 3.24; Diagram 3.4

D

doorways on approach routes 2.15, 3.15 external doors 2.21 principal communal entrance 1.9, 2.15–2.15, 3.14–3.15 principal private entrance 2.20, 3.22; Diagram 3.3 internal, Category 1 1.15; Table 1.1; Diagram 1.2 internal, Category 2 2.22; Table 2.1; Diagram 2.3 internal, Category 3 3.24; Diagrams 3.4, 3.5 see also clear opening width

drop-off points 2.13, 3.13

E

#

Source page 66

entrances see communal entrances; private entrances; principal communal entrances; principal private entrances

entrance storey 1.13–1.18 kitchen and eating areas 3.32 principal bedroom 3.35 WC facilities 1.17, 2.27, 3.37–3.39 wheelchair storage 3.25

Equality Act 2010 0.9

F

furniture schedule Appendix D

H

habitable rooms Category 2 2.24–2.25 Category 3 3.31–3.35

Halls see corridors

historic buildings 0.12–0.13

K

kitchens wheelchair accessible dwellings 3.32, 3.34; Table 3.4; Diagram 3.8 wheelchair adaptable dwellings 3.32, 3.33; Table 3.3

L

legislation 0.7–0.9 Building Regulations 2010 0.14, 0.15 Equality Act 2010 0.9 Equality Act 2010 (Disability) Regulations 0.9 The Workplace (Health, Safety and Welfare) Regulations 0.7–0.8

lifts wheelchair accessible dwellings 3.29; Diagram 3.7 wheelchair adaptable dwellings 3.28 see also communal lifts

living area 2.24, 3.31; Table 3.2

M

material alterations 0.11 mixed use development 0.10

O

optional requirements 0.3–0.6

P

parking spaces 2.12, 3.12

principal bedroom 2.25

principal communal entrances 1.9, 2.14, 3.14

principal private entrances Category 2 2.20 Category 3 3.22; Diagram 3.3

principal storey WC facilities 1.27

private entrances Category 1 1.13–1.14 Category 2 2.20–2.21

private outdoor space 3.45

R

ramps on approach route 1.7, 2.10, 3.10 maximum length for gradient Diagrams 2.1, 3.1

S

sanitary facilities Category 1 1.17 Category 2 2.26–28 Category 3 3.36–3.43; Table 3.5 see also bathrooms; WC facilities

sanitary fittings Diagram 2.5 wheelchair accessible dwellings Diagrams 3.11, 3.16, 3.17 wheelchair adaptable dwellings Diagrams 3.10, 3.14

services 1.18, 2.30, 3.44; Diagram 1.5

showers 2.27, 3.36–3.39, 3.41; Table 3.5; Diagram 2.5, see also bathrooms, sanitary fittings

stairs communal 1.10, 1.12 private 2.23, 3.30

V

#

Source page 67

stepped approach Category 1 1.8 Category 2 2.11 Category 3 3.11

steps see stepped approach

storage space general storage 3.26; Table 3.1 wheelchair storage and transfer 3.25; Diagram 3.6

V

visitable dwellings 1.1–1.18

W

WC access zones Diagrams 1.3, 3.13, 3.14 wheelchair accessible dwellings Diagram 3.11 wheelchair adaptable dwellings Diagram 3.10

WC facilities Category 1 1.17; Diagram 1.4 Category 2 2.27; Diagram 2.6 Category 3 3.36–3.40; Diagrams 3.11–3.14

wheelchair user dwellings 3.1–3.45

wheelchair accessible dwellings bathrooms 3.43; Diagrams 3.11, 3.16, 3.17 kitchens 3.34; Table 3.4; Diagram 3.3 lifting devices 3.29; Diagram 3.7 optional requirement 0.5 WC facilities 3.36, 3.39; Diagrams 3.11, 3.12

wheelchair adaptable dwellings bathrooms 3.42; Diagrams 3.10, 3.15 kitchens 3.33; Table 3.3 lifting devices 3.28 storage space 3.25 WC facilities 3.36, 3.38; Diagrams 3.10, 3.12

Workplace (Health, Safety and Welfare) Regulations 0.7–0.8

worktops Tables 3.3, 3.4

List of approved documents

#

Source page 68

The following documents have been published to give guidance on how to meet the Building Regulations. You can find the date of the edition approved by the Secretary of State at www.gov.uk.

Approved Document A Structure

Approved Document B Fire safety Volume 1: Dwellinghouses Volume 2: Buildings other than dwellinghouses

Approved Document C Site preparation and resistance to contaminants and moisture

Approved Document D Toxic substances

Approved Document E Resistance to the passage of sound

Approved Document F Ventilation

Approved Document G Sanitation, hot water safety and water efficiency

Approved Document H Drainage and waste disposal

Approved Document J Combustion appliances and fuel storage systems

Approved Document K Protection from falling, collision and impact

Approved Document L1A Conservation of fuel and power in new dwellings

Approved Document L1B Conservation of fuel and power in existing dwellings

Approved Document L2A Conservation of fuel and power in new buildings other than dwellings

Approved Document L2B Conservation of fuel and power in existing buildings other than dwellings

Approved Document M Access to and use of buildings Volume 1: Dwellings Volume 2: Buildings other than dwellings

Approved Document P Electrical safety – Dwellings

Approved Document Q Security – Dwellings

Approved Document 7 Materials and workmanship

Page 69

#

Source page 69

Published by NBS, part of RIBA Enterprises Ltd, and available from:

RIBA Bookshops Mail Order The Old Post Office, St Nicholas Street Newcastle Upon Tyne, NE1 1RH

Telephone orders/General enquiries: +44 (0)191 244 5557 Email orders: sales@ribabookshops.com Or order online at: www.ribabookshops.com

ISBN 978 1 85946 747 3

© Crown copyright, 2015

You may re-use this information (excluding logos) free of charge in any format or medium, under the terms of the Open Government Licence v3. To view this licence, visit www.nationalarchives.gov.uk/doc/open-government-licence/version/3/ or write to the Information Policy Team, The National Archives, Kew, London TW9 4DU or email psi@nationalarchives.gsi.gov.uk. Where we have identified any third-party copyright information, you will need to obtain permission from the copyright holders concerned. This publication is available for download at www.gov.uk.

Copyright in the typographical arrangement, excluding logos, of the cover and internal page layouts of this publication rests with the Publisher.

www.thenbs.com

ISBN 978 1 85946 747 3