Part J · England · Free to use

Combustion air vent calculator

Permanent ventilation for open-flued stoves, boilers and fires by fuel, output and airtightness.

Approved Document J (2022)

Your inputs

Results update as you type.

Fuel
kW
Draught stabiliser fitted
Design air permeability 5 or below

Part J · Result

1,650 mm² permanent vent

550 mm² per kW above 5 kW.

Calculated result
  • Rated output: Calculated result8 kW
  • Minimum free area: Calculated resultappliance in the room, direct to outside1,650 mm²
  • Room-sealed appliances need no room vent. Appliances in a compartment need the larger vents in Diagrams 32 and 40.
  • Pre-2008 homes are unlikely to be below 5 m³/(h·m²).

Clauses this relies on

Source edition and scope

Approved Document J (2022).

Gas calculations cover open-flued appliances in a room with direct ventilation to outside, excluding decorative fuel-effect and flueless appliances. The first 7 kW net input can be ignored only in older dwellings with air permeability above 5 m³/(h·m²), as stated in Diagram 32 note 5.

This is a preliminary check of the conditions shown. Confirm the edition, project circumstances and any additional requirements with your architect or building control.

A design aid, not legal advice. Checked against the Building Regulations 2010 for England; confirm with building control.