Part B · England · Free to use

Escape stair capacity calculator

People a stair can carry for simultaneous evacuation (Table 3.2) or the width needed for phased evacuation.

Approved Document B Volume 2, Tables 3.1 to 3.3

Your inputs

Results update as you type.

Evacuation
mm

Simultaneous: everyone on all storeys served. Phased: the most people on any one storey.

Part B · Result

Carries 465 people

2 stairs, 6 storeys, simultaneous evacuation.

Checks passed
  • People per stair, one stair discounted: Calculated result420 ÷ 1420
  • Stair capacity: Checks passed1,200 mm stair serving 6 storeys (Table 3.2)465 people
  • Capacity by formula: Calculated resultP = 200W + 50(W − 0.3)(N − 1)465 people
  • Stair width: Checks passedmin 1,000 mm for over 50 people; 1,100 mm for assembly1,200 mm
  • Where there is more than one stair, assume the largest is unavailable (para 3.17), so capacity is shared by the rest.
  • Table 3.2 is read with the stair width rounded down to the nearest column; over 10 storeys extrapolate.

Clauses this relies on

Source edition and scope

Approved Document B Volume 2, Tables 3.1 to 3.3.

This is a preliminary check of the conditions shown. Confirm the edition, project circumstances and any additional requirements with your architect or building control.

A design aid, not legal advice. Checked against the Building Regulations 2010 for England; confirm with building control.