How to specify internal doors
What an internal timber doorset clause has to cover when the door is not a fire door, the decisions behind it, the standards to cite, and how to write it in CAWS and in Uniclass.
Photo: Tomwsulcer, CC0, via Wikimedia Commons.
How do you specify internal doors?
To specify internal doors, specify a factory-made timber doorset rather than a loose leaf and frame: state the leaf construction and thickness, facing and lipping, frame profile, duty class to BS EN 1192, clear opening width, glazing and any acoustic seals. Confirm with the fire strategy that each door really is a non-fire door, then let the door schedule give each opening its type, size, handing and ironmongery set.
The doors that are not fire doors get the least attention in most specifications. They are often covered by one line, "internal doors to be hardwood-lipped flush doors in softwood frames", with everything else left to the joinery supplier. That line does not say how heavy the leaf is, so nobody can check the hinges. It does not give a clear width, so the accessible WC door is sized from the leaf. It says nothing about the gap at the bottom, which is where ventilation and acoustic requirements meet.
This guide covers internal timber doorsets under Uniclass Pr_30_59_24_97 Wood doorsets, for offices, schools, housing and healthcare where the door has no fire rating. Fire-resisting doorsets use the same code but bring their own certification rules, which are covered in how to specify fire doors. Where leaf and frame are bought separately, the leaf has its own codes, Pr_30_59_23_97 Wood flush door leaves and Pr_30_59_23_98 Wood panelled door leaves.
What does a internal door clause need to cover?
Some properties are specific to internal doors. Others belong in every product clause. A clause that leaves either out gives the contractor room to substitute.
Properties of internal doors
- Threshold detailLevel threshold and the undercut to the finished floor.
- Operation methodManual hinged in this guide.
- Smoke controlNever guessNone, once the fire strategy confirms it.
- Reaction to fire classificationNever guessOnly where the fire strategy sets one for doors.
- AccessoriesArchitraves, stops, kick plates and door signs.
- Third-party certificationNever guessNot needed for non-fire doors; say so.
- Safety glazing classificationNever guessBS EN 12600 class for glazed leaves and side panels.
- Frame profileRebated or planted stop, sized to the wall.
- AccessibilityEffective clear width, vision panels, opening force.
- FixingsNever guessFrame fixings and packing to the maker's instructions.
- Acoustic performanceRw for meeting rooms, classrooms and consulting rooms.
- Moisture contentTimber dry enough to stay flat once heated.
- Glazing specificationVision panel size, glass type and beads.
- Fire resistanceNever guessNone, confirmed against the fire strategy.
- IronmongerySets from the ironmongery schedule, suited to leaf weight.
- FacingPaint grade, veneer or laminate.
- Edge treatmentNever guessLipping type, species and thickness.
- Category of useBS EN 1192 duty class for the traffic.
- Timber speciesFrame and lipping species, matched to the finish.
- Opening configurationSingle, double, leaf and a half, fanlight.
- ThicknessNever guessLeaf thickness, which sets weight and hinge choice.
- Door leaf constructionCore type, stiles and rails, facings.
- Glass manifestationNever guessLarge glazed leaves and side panels on circulation routes.
- Appearance classBS EN 942 class for frames, set by the finish.
- Perimeter sealsNever guessAcoustic or draught seals, or none.
- Coat build-upFactory lacquer or primer system and coats.
What every product clause needs
- Manufacturer and product referenceDoorset maker and range, or a performance description.
- Product standardBS EN 14351-2 for internal pedestrian doorsets, where declared.
- Installation methodDoorset maker's fixing instructions plus this clause.
- Technical submittalsData sheets, duty class and acoustic test evidence.
- Operation and maintenance informationHinge adjustment, finish care and spare parts.
- MaterialTimber frame with timber-based leaf.
- FinishFactory finish or primed for site decoration.
Uniclass Pr_30_59_24_97 Wood doorsets. Not every property applies to every project; where one does not, say so rather than leaving it blank.
Fields marked Never guess depend on the project and should never be filled from a default or a previous job. If the information is not available yet, the clause should say so with a TBC and a reason.
Which decisions does the clause depend on?
Most properties follow from the product you choose. These depend on the project, so they need a decision from the designer before the clause is written.
- 01
Confirm it is not a fire door
Never guessA non-fire internal door is a decision, not a default. Doors to stores, plant rooms, kitchens and some corridors are often fire doors in the fire strategy even when the plans show nothing. If the clause treats the door as a plain doorset, no fire resistance, smoke control or third-party certification is asked for, and the gap is found at the fire engineer's site inspection. Doors on escape routes can still carry a reaction to fire classification for their surfaces if the strategy sets one, even when they have no fire resistance.
How to decide
- Check every door number on the schedule against the fire strategy drawings before choosing this clause.
- Where the strategy shows no rating, write fire resistance, smoke control and third-party certification as "not required" rather than leaving the lines out.
- Ask the fire engineer whether doors on escape routes need a reaction to fire classification, and state it if they do.
- Move any door that turns out to be rated onto the fire doorset type, not this one.
Write it asFire resistance: Not required (non-fire-resisting doorset, confirmed against fire strategy drawings). Smoke control: Not required. - 02
Clear width, not leaf width
AccessApproved Document M sets door widths as effective clear widths: the gap you can get a wheelchair through, measured at right angles to the wall from the stop on the latch side to the nearest obstruction on the hinge side, such as the open leaf, its stop or projecting door furniture. A 926 mm leaf does not give 926 mm of clear width. Volume 2 gives minimum effective clear widths for buildings other than dwellings, for example 800 mm for a straight-on approach in a new building, more where the approach is from a narrower corridor at right angles. Dwellings built to M4(2) or M4(3) have their own figures in Volume 1.
How to decide
- Find the clear width each door needs from Approved Document M for the building type and approach direction.
- Work back to the leaf size using the doorset maker's frame, stop and leaf thickness, and the handle projection.
- Add vision panels where Approved Document M and BS 8300-2 call for them, for example doors across corridors.
- Put the required clear width in the door schedule as well as the leaf size, so both can be checked.
Write it asAccessibility: Effective clear width not less than the figure in the door schedule, measured as Approved Document M Volume 2. Submit calculation for each leaf size. - 03
Leaf construction, thickness and lippings
LeafThe core decides almost everything else: weight, screw holding for hinges and closers, sound reduction and how well the leaf stays flat. A hollow-core leaf suits light domestic use. Commercial doors need a solid or semi-solid core, with hardwood lippings thick enough to take the hinges and to survive trolleys. Leaf thickness (commonly 35 or 40 mm in housing, 44 mm or more in commercial work) follows from the core. The edge treatment, exposed or concealed lippings, should match the finish, because a concealed lipping under a veneer cannot be planed much on site. Frame fixings and packing positions belong to the doorset maker's instructions, so cite them rather than inventing centres.
How to decide
- Set the duty class to BS EN 1192 first, from the traffic: light for domestic, medium or heavy for offices, severe for schools and healthcare.
- Choose the core and thickness that the doorset maker tests for that duty class.
- Specify hardwood lippings to the hanging and leading edges at least, with species to suit the facing.
- Cite the maker's installation instructions for frame fixings, packing and gaps.
Write it asDoor leaf: Solid core, 44 mm thick, hardwood lippings to all edges. Strength: Class 3 (heavy duty) to BS EN 1192. - 04
Vision panels and glazed leaves
Never guessMost glass in door leaves and in side panels next to doors is in a critical location under Approved Document K, so it has to be safety glass. The BS EN 12600 class follows from the size of the pane and where it sits, and a vision panel in a classroom door is not the same as a fully glazed meeting room door. Large glazed leaves and side panels on circulation routes also need glass manifestation at the heights Approved Document K gives. Leave these to the glazier and you get toughened glass with no class on the delivery note and no manifestation until a snag list.
How to decide
- List every glazed door type and side panel and its pane size.
- Set the safety glazing classification to BS EN 12600 for each, following Approved Document K.
- Decide whether laminated glass is needed for acoustic reasons as well; it changes the glass but not the safety class.
- Say who supplies and fixes the glass manifestation, and that it is on the door schedule.
Write it asGlazing: Laminated safety glass, Class 2(B)2 to BS EN 12600, in hardwood beads as doorset maker's standard. Glass manifestation: As Approved Document K, on all fully glazed leaves. - 05
Acoustic seals and the gap at the bottom
Sound and airTwo requirements pull against each other at the foot of the door. Approved Document F expects internal doors in dwellings to let air through, with a free area equivalent to a 10 mm undercut in a 760 mm wide door (about 7,600 mm²), measured above the floor finish, or 20 mm above the floor surface where the finish is not yet laid. Meeting rooms, consulting rooms and classrooms need the opposite: perimeter seals and a drop seal, with the acoustic rating tested on the whole doorset. Approved Document E does not set a figure for internal doors in dwellings, so for other buildings the target usually comes from the acoustic consultant, BB93 for schools or HTM 08-01 for healthcare.
How to decide
- For dwellings, state the undercut measured from the finished floor, not the screed.
- For rooms with a sound insulation target, ask the acoustic consultant for the doorset Rw.
- Specify the perimeter seals and threshold seal as tested with that rating.
- Where a sealed door is also on a ventilation path, check with the services engineer how air gets out of the room.
Write it asAcoustic performance: Rw not less than 30 dB for the complete doorset, laboratory tested. Perimeter seals: Acoustic seals to head and jambs and automatic drop seal, as tested.
The values under "Write it as" are examples. The right value depends on the location, the use and the fire strategy.
Which standards should the clause cite?
Cite the product standard the declaration of performance refers to, the code of practice for installation, and the test method behind each value you set. A value without its test method cannot be checked against a submittal.
- BS EN 14351-2
- Windows and doors. Product standard, performance characteristics. Internal pedestrian doorsets
The European product standard for internal pedestrian doorsets, excluding fire resistance and smoke control. It lists the characteristics a maker can declare, such as acoustic performance, mechanical strength and operating forces.
In the clause Cite it where the maker declares to it, and ask for the test report behind each property: "Doorset to BS EN 14351-2, declared performance to be submitted".
- BS 4787-1
- Internal and external wood doorsets, door leaves and frames. Specification for dimensional requirements
UK coordinating sizes for wood doorsets, leaves and frames. Still current, and the source of the familiar 2040 mm height and metric leaf widths.
In the clause Use it when the leaves are standard sizes: "Leaf sizes: To BS 4787-1, as door schedule".
- BS EN 1192
- Doors. Classification of strength requirements
Classes 1 to 4 (light, medium, heavy and severe duty) for resistance to vertical load, torsion and impact.
In the clause "Strength: Class 3 (heavy duty) to BS EN 1192."
- BS EN 942
- Timber in joinery. General requirements
Appearance classes (J2 to J50) for timber in joinery, and moisture content at delivery.
In the clause "Frames: Hardwood to BS EN 942, appearance class J10 for clear finish."
- BS EN 12600
- Glass in building. Pendulum test. Impact test method and classification for flat glass
The impact classes, such as 1(B)1 and 2(B)2, used to show glass is safe in critical locations.
In the clause "Glazing: Class 2(B)2 to BS EN 12600."
- BS 8300-2
- Design of an accessible and inclusive built environment. Buildings. Code of practice
Guidance on door widths, vision panels, ironmongery, visual contrast and opening forces, in more detail than Approved Document M.
In the clause "Door leaf and frame to contrast visually with the surrounding wall, as BS 8300-2."
- BS EN 13501-1
- Fire classification of construction products and building elements. Classification using data from reaction to fire tests
The Euroclass system for surfaces, used where the fire strategy sets a reaction to fire class for doors on escape routes.
In the clause "Reaction to fire: Class B-s3,d2 to BS EN 13501-1, where scheduled."
Confirm the current edition of each standard at every issue. Avoice's State of UK Specifications 2026 found a withdrawn standard cited in 40% of specifications at contract issue.
For the regulations behind these choices, see Approved Document M explained, Approved Document K explained, or search the Avoice Regulations library.
How do you write it in CAWS?
In CAWS, internal doorsets are written in L20 as product clauses in the 400s, one for each door type on the door schedule. A wood doorset clause covers the leaf (core, thickness, facings, lippings, finish), the frame and architraves, glazing and beads, ironmongery reference, seals, strength and any acoustic or access requirements. The door schedule then gives each door its type, size and handing.
L20 also has a general clause for non-fire-resisting doors, which sits beside the fire door clause, and execution clauses for fixing doorsets, fixing wood frames, fitting ironmongery and hinge positions. A project with veneered meeting room doors and paint-grade office doors has two type clauses sharing those general clauses.
- Description
- Internal hinged doorset, not fire-resisting
- Manufacturer
- Submit proposals
- Door leaf core
- Solid core
- Thickness
- 44 mm
- Facings
- TBC Client choice between oak veneer and paint-grade facing outstanding. Resolve before ordering.
- Lippings
- Hardwood, exposed, to all four edges
- Finish as delivered
- Factory finished
- Frame and architraves
- Hardwood frame with planted stop, appearance class J10 to BS EN 942, architraves as drawings
- Glazing
- Vision panels as door schedule, laminated safety glass Class 2(B)2 to BS EN 12600
- Ironmongery
- Sets as ironmongery schedule, hinges rated for leaf weight
- Strength
- Class 3 (heavy duty) to BS EN 1192
- Fire resistance
- Not required, confirmed against fire strategy drawings
- Accessibility
- Effective clear width as door schedule, measured as Approved Document M
- Acoustic performance
- Not required unless stated on door schedule
- Threshold
- Level, undercut as door schedule measured from finished floor
- Fixing
- Frame fixings and packing as doorset maker's instructions
Illustrative, not from a real project. One property is left as a TBC with a reason so it can be tracked and closed before issue.
Clauses the type clause relies on
- L20/110
- Evidence of performance Test reports and data for strength, acoustic and glazing claims, submitted before ordering.
- L20/120
- Non-fire-resisting pedestrian doors/ door assemblies/ doorsets General requirement for certified evidence that doors with no fire rating meet the specified performance.
- L20/170
- Control samples A finished sample door and frame approved before the order is placed.
- L20/750
- Fixing doorsets Fixing the complete doorset plumb, square and to the maker's instructions.
- L20/830
- Fixing ironmongery generally Cutting in and fixing hardware without weakening the leaf.
- L20/850
- Location of hinges Hinge positions and number per leaf.
Clause numbers vary between NBS versions and practice masters. These follow the L20 section of a published NBS-format refurbishment specification; check that each clause your type clause refers to exists in your own L20.
How do you write it in Uniclass?
In Uniclass the door in its opening is a system and the doorset is a product. For a hinged internal door the system is Ss_25_30_20_39 Hinged doorset systems. It describes the doorset in the wall: how it is fixed, the finished floor and undercut, the ironmongery set, and what the installed door must achieve for access and sound.
The doorset itself is a product clause under Pr_30_59_24_97 Wood doorsets, holding leaf construction, facings, lippings, frame, glazing and strength class. Write two product clauses if the project has two leaf types, and point each hinged doorset system at the right one. Fire doors go under the same Pr code but in their own product clauses, so a change to the plain doors never touches the certified ones.
- Description
- Internal hinged timber doorset, not fire-resisting
- Doorset
- Pr_30_59_24_97 Wood doorsets (D10)
- Ironmongery
- Sets as ironmongery schedule
- Fixing
- Frame fixed and packed as doorset maker's instructions
- Threshold
- Level, undercut as door schedule measured from finished floor
- Clear width
- As door schedule, measured as Approved Document M
- Fire resistance
- Not required, confirmed against fire strategy drawings
- Manufacturer
- Submit proposals
- Door leaf core
- Solid core
- Thickness
- 44 mm
- Facings
- TBC Client choice between oak veneer and paint-grade facing outstanding. Resolve before ordering.
- Lippings
- Hardwood, exposed, to all four edges
- Frame
- Hardwood with planted stop, appearance class J10 to BS EN 942
- Glazing
- Vision panels as door schedule, Class 2(B)2 to BS EN 12600
- Strength
- Class 3 (heavy duty) to BS EN 1192
- Finish
- Factory finished
- Moisture content
- To BS EN 942, suited to a heated interior; values at delivery to be submitted
Illustrative. Performance of the finished system sits in the system clause; properties of the product sit in the product clause.
In NBS Chorus, Uniclass product clauses also carry an NBS reference (for wood doorsets, 45-25-28/348); keep CAWS and Uniclass references out of the same specification.
What goes in the spec, and what goes in the schedule?
The specification defines each type once. The schedule and drawings say where each type goes.
In the specification
What the product is and how it performs and is installed. Written once per type.
In the schedule or drawings
Where each type goes and how much of it. Changes with every plan revision.
Write each door type once with a type mark (D10, D11) and let the door schedule carry sizes, handing, clear widths and ironmongery sets. When a door turns out to need a fire rating, it changes type on the schedule rather than gaining a line in the plain doorset clause.
For coordination between these documents, see Why your window and door schedules don’t match your specification.
What are the common mistakes?
Most problems are a missing property, a property filled with the wrong kind of value, or a decision left silently open.
- Leaf width in place of clear width. The accessible WC door is drawn at 926 mm and assumed compliant. Once the stop, leaf thickness and lever handle are deducted it may fall short. Schedule the clear width and ask for the calculation.
- "Solid core" with nothing behind it. Particleboard, timber strip and tubular cores are all sold as solid or semi-solid. Tie the core to a BS EN 1192 duty class and to the maker's test evidence.
- Hinges picked before the leaf is known. A heavy veneered acoustic leaf on standard hinges drops within a year. Give the leaf weight to the ironmonger, or require hinges graded for it.
- Undercut measured from the screed. If the floor finish goes down after the doors are hung, a 10 mm undercut becomes 2 mm. Say the undercut is measured from the finished floor.
- Frames ordered before the walls are built. Partition thickness changes with the lining and the acoustic build-up. Fix the frame depth to the wall type, or ask for adjustable frames, before ordering.
- Two descriptions of the same door. The door schedule says "glazed" while the clause says "solid". Keep vision panels on the schedule only and let the clause give the glass class.
How Avoice helps
Avoice drafts internal doorset clauses from your door schedule and plans, and shows which doors it could not resolve.
- Drafts from the door schedule
It reads door types, leaf sizes and ironmongery sets from your door schedule, writes the L20 or Uniclass clause for each type, and fills in the leaf, frame and glazing lines your information supports.
- Leaves a TBC where a choice is open
If the client has not chosen between veneer and paint grade, or the acoustic consultant has not given an Rw for the meeting rooms, the clause says TBC with the reason. Every TBC goes into one project register to close before tender.
- Writes in your format
CAWS L20 type clauses or Uniclass hinged doorset systems with Pr product clauses, adapted from your practice's own master clauses.
- Checks doors against the drawings
QA/QC flags a D12 on the plans with no clause, a plain doorset on a door the fire strategy marks as FD30, a reference to an L20 clause your master does not contain, or a withdrawn standard.
- Keeps the evidence with the clause
Doorset data sheets and test reports sit in the Product Room, linked to the clause. Edit the linked doorset once and every door type that uses it updates. Approved Documents K and M are in the Avoice Regulations library for checking glazing and widths.
Related guides: How to specify fire doors, How to specify door hinges, How to specify door handles.
Software can draft and check. The designer still chooses the product and is responsible for the specification.
Draft your internal door clause in Avoice
Upload your drawings and schedules. Avoice drafts the clause in CAWS or Uniclass, cites the standards and flags anything your information does not settle.
This guide is for general education and is not professional advice. Check current editions of standards and Approved Documents, the manufacturer's data, and the requirements of your project before relying on any clause.